89System Heating Performance Data (Cont.)Ducted Split System53QDMT60-518 Heat Pump380-420V/3Ph/50HzIndoor Conditions Outdoor Ambient TemperatureESPin.wgFanSpeedAirFlowcfmTemp. °CDB24/18°C DB/WB 7/6°C DB/WB 2/1°C DB/WBCapacityBtu/hrInputWCapacityBtu/hrInputWCapacityBtu/hrInputW0.36in.wgHigh 119015°C 63700 4270 51450 3685 42150 317020°C 61740 4670 49000 3965 39700 350027°C 57810 4960 46055 4280 37240 3765Medium 109515°C 60515 4100 48880 3540 40045 304520°C 58655 4485 46550 3810 37715 336027°C 54920 4765 43755 4110 35380 3615Low 60315°C 55070 3775 44480 3255 36440 280020°C 53375 4125 42365 3505 34325 309527°C 49980 4385 39815 3785 32195 33300.40in.wgHigh 115915°C 62790 4245 50715 3660 41545 315020°C 60860 4645 48300 3940 39130 347027°C 56980 4935 45395 4255 36705 3745Medium 106415°C 59655 4080 48180 3515 39470 302520°C 57820 4460 45885 3785 37175 333527°C 54135 4740 43130 4085 34870 3600Low 57815°C 54285 3750 43845 3235 35920 278520°C 52615 4105 41760 3480 33830 306527°C 49260 4360 39245 3760 31735 331042QDMT60-71838QDMT60-518