78Table 11 — CVC/ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting GuidesA. MANUAL STOPB. READY TO STARTC. IN RECYCLE SHUTDOWNPRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDYMANUALLY STOPPED — PRESS CCN OR LOCAL TO START PIC II in OFF mode, press CCN or LOCAL softkey to start unit.TERMINATE PUMPDOWN MODE TO SELECT CCN OR LOCAL Enter the CONTROL TEST table and select TERMINATE LOCKOUT tounlock compressor.SHUTDOWN IN PROGRESS COMPRESSOR UNLOADING Chiller unloading before shutdown due to soft/stop feature.SHUTDOWN IN PROGRESS COMPRESSOR DEENERGIZED Chiller compressor is being commanded to stop. Water pumps aredeenergized within one minute.ICE BUILD OPERATION COMPLETE Chiller shutdown from Ice Build operation.PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDYREADY TO START IN XX MIN UNOCCUPIED MODE Time schedule for PIC II is unoccupied. Chillers will start only whenoccupied.READY TO START IN XX MIN REMOTE CONTACTS OPEN Remote contacts are open. Close contacts to start.READY TO START IN XX MIN STOP COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to stop. Releasepoint to start.READY TO START IN XX MIN OCCUPIED MODE Chiller timer counting down. Unit ready to start.READY TO START IN XX MIN REMOTE CONTACTS CLOSED Chiller timer counting down. Unit ready to start. Remote contact enabledand closed.READY TO START IN XX MIN START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to start. Releasevalue to start under normal control.READY TO START IN XX MIN RECYCLE RESTART PENDING Chiller in recycle mode.READY TO START UNOCCUPIED MODE Time schedule for PIC II is unoccupied. Chiller will start when occupied.Make sure the time and date are correct. Change values in TIME ANDDATE screen.READY TO START REMOTE CONTACTS OPEN Remote contacts have stopped the chiller. Close contacts to start.READY TO START STOP COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to stop. Releasepoint to start.READY TO START OCCUPIED MODE Chiller timers complete, unit start will commence.READY TO START REMOTE CONTACTS CLOSED Chiller timer counting down. Unit ready for start.READY TO START START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT has been manually forced to start.Chiller will start regardless of time schedule or remote contact status.STARTUP INHIBITED LOADSHED IN EFFECT CCN loadshed module commanding chiller to stop.PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDYRECYCLE RESTART PENDING OCCUPIED MODE Unit in recycle mode, chilled water temperature is not sufficientlyabove set point to start.RECYCLE RESTART PENDING REMOTE CONTACT CLOSED Unit in recycle mode, chilled water temperature is not sufficientlyabove set point to start.RECYCLE RESTART PENDING START COMMAND IN EFFECT Chiller START/STOP on MAINSTAT manually forced to start, chilledwater temperature is not sufficiently above set point to start.RECYCLE RESTART PENDING ICE BUILD MODE Chiller in ICE BUILD mode. Chilled fluid temperature is satisfied forICE BUILD conditions.