11Table 4 — ICVC Alert CodesPRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset isnecessary.*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] isthe actual pressure, temperature, voltage, etc., at which the control tripped.ICVC FAULTSTATEPRIMARYMESSAGESECONDARYMESSAGE PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY100 PRESTARTALERTSTARTS LIMITEXCEEDED100Excessive compressor starts(8 in 12 hours).Depress the RESET softkey if additional startis required. Reassess start-up requirements.101 PRESTARTALERTHIGH BEARINGTEMPERATURE101Comp Thrust Brg Temp [VALUE]exceeded limit of [LIMIT]*.Check oil heater for proper operation.Check for low oil level, partially closed oil sup-ply valves, clogged oil filters.Check the sensor wiring and accuracy.Check Comp Thrust Brg Alert setting inSETUP1 screen.102 PRESTARTALERTHIGH MOTORTEMPERATURE102Comp Motor Winding Temp[VALUE] exceeded limit of [LIMIT]*.Check motor sensors for wiring and accuracy.Check motor cooling line for proper operation,or restrictions.Check for excessive starts within a short timespan.Check Comp Motor Temperature Overridesetting in SETUP1 screen.103 PRESTARTALERTHIGHDISCHARGETEMP103Comp Discharge Temp [VALUE]exceeded limit of [LIMIT]*.Allow discharge sensor to cool.Check sensor wiring and accuracy.Check for excessive starts.Check Comp Discharge Alert setting inSETUP1 screen.104 PRESTARTALERTLOWREFRIGERANTTEMP104Evaporator Refrig Temp [VALUE]exceeded limit of [LIMIT]*.Check transducer wiring and accuracy.Check for low chilled fluid supplytemperatures.Check refrigerant charge.Check Refrig Override Delta T in SETUP1screen.105 PRESTARTALERTLOW OILTEMPERATURE105Oil Sump Temp [VALUE]exceeded limit of [LIMIT]*.Check oil heater contactor/relay and power.Check oil level and oil pump operation.106 PRESTARTALERTHIGHCONDENSERPRESSURE106Condenser Pressure [VALUE]exceeded limit of [LIMIT]*.Check transducer wiring and accuracy.Check for high condenser watertemperatures.Check high condenser pressure switch wiring.107 PRESTARTALERTLOW LINEVOLTAGE107Percent Line Voltage [VALUE]exceeded limit of [LIMIT]*.Check voltage supply.Check voltage transformers and switch gear.Consult power utility if voltage is low.108 PRESTARTALERTHIGH LINEVOLTAGE108Percent Line Voltage [VALUE]exceeded limit of [LIMIT]*.Check voltage supply.Check power transformers.Consult power utility if voltage is high.109 PRESTARTALERTGUIDE VANECALIBRATION109Actual Guide Vane PosCalibration Required Before Startup.Press STOP button on ICVC and performGuide Vane Calibration in Controls Testscreen.Check guide vane actuator feedbackpotentiometer.110 PRESTARTALERTHIGHRECTIFIERTEMP110Rectifier Temperature [VALUE]exceeded limit of [LIMIT]*.Check that VFD refrigerant isolation valvesare open.Check VFD refrigerant cooling solenoid andrefrigerant strainer.Check for proper VFD cooling fan operationand blockage.111 PRESTARTALERT HIGHINVERTERTEMP111Inverter Temperature [VALUE]exceeded limit of [LIMIT]*. Check that VFD refrigerant isolation valvesare open.Check VFD refrigerant cooling solenoid andrefrigerant strainer.Check for proper VFD cooling fan operationand blockage.