11CARE AND MAINTENANCEFor continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment.Frequency of maintenance may vary depending upon geographic areas, such as coastal applications. See Owner’s Manual for information.Table 4—Required Liquid ---Line Temperature (°F)LIQUIDPRESSUREAT SER-VICE VALVE(PSIG)REQUIRED SUBCOOLING TEMPERATURE (°F)8 10 12 14 16 18189 58 56 54 52 50 48195 60 58 56 54 52 50202 62 60 58 56 54 52208 64 62 60 58 56 54215 66 64 62 60 58 56222 68 66 64 62 60 58229 70 68 66 64 62 60236 72 70 68 66 64 62243 74 72 70 68 66 64251 76 74 72 70 68 66259 78 76 74 72 70 68266 80 78 76 74 72 70274 82 80 78 76 74 72283 84 82 80 78 76 74291 86 84 82 80 78 76299 88 86 84 82 80 78308 90 88 86 84 82 80317 92 90 88 86 84 82326 94 92 90 88 86 84335 96 94 92 90 88 86345 98 96 94 92 90 88354 100 98 96 94 92 90364 102 100 98 96 94 92374 104 102 100 98 96 94384 106 104 102 100 98 96395 108 106 104 102 100 98406 110 108 106 104 102 100416 112 110 108 106 104 102427 114 112 110 108 106 104439 116 114 112 110 108 106450 118 116 114 112 110 108462 120 118 116 114 112 110474 122 120 118 116 114 112486 124 122 120 118 116 114499 126 124 122 120 118 116511 128 126 124 122 120 118LEGEND24--V FACTORY WIRING24--V FIELD WIRINGFIELD SPLICE CONNECTIONCONTACTORCA05379Fig. 9 --- — Generic Wiring Diagrams(See Thermostat Installation Instructions for specific unit combinations)24ACA24ACA