Appendix C: 30MP Multi-chiller Points/Properties30MP Multi-chiller CARRIER CORPORATION ©2018Installation and Start-up Guide All rights reserved40Lvg Load Water Temp Alarm – Enables leaving load water temperature failure alarm. D:R:EnableDisable/EnableLvg Load Wtr Sensor Alarm – Enables leaving load water temperature alarm. D:R:EnableDisable/EnableEnt Load Water Temp Alarm – Enables entering load water temperature alarm. D:R:EnableDisable/EnableEnt Load Wtr Sensor Fail Alarm – When set to Enable, any Entering Load Water SensorFailure Alarm indicated by the controller also initiates an Equipment Alarm andenergizes the Alarm Lamp binary output.D:R:EnableDisable/EnableOA Temperature Alarm – When set to Enable, any Outdoor Air Temperature Alarmindicated by the controller also initiates an Equipment Alarm and energizes the AlarmLamp binary output.D:R:EnableDisable/EnableOA Sensor Failure Alarm – When set to Enable, an Outdoor Air Temperature SensorFailure Alarm indicated by the controller also initiates an Equipment Alarm andenergizes the Alarm Lamp binary output.D:R:EnableDisable/EnableHigh RH Alarm – When set to Enable, a High Space Relative Humidity Alarm indicated bythe controller also initiates an Equipment Alarm and energizes the Alarm Lamp binaryoutput.D:R:EnableDisable/EnableRH Sensor Fail Alarm – When set to Enable, a Relative Humidity Sensor Failure Alarmindicated by the controller also initiates an Equipment Alarm and energizes the AlarmLamp binary output.D:R:EnableDisable/EnableMaintenanceNavigation: i-Vu® / Field Assistant: Properties > Control Program > MaintenancePoint Name/Description RangeUnitUnit Type – The type of equipment that the controller is controlling. R: AirWaterControlling Point – Displays the point used to control this equipment. R: Leaving Water TempEntering Water TempChiller Size Compare - Indicates whether chillers are equal or unequal size. R: EqualUnequalExt Demand Limit Status – The external demand limit input status. R: Off/OnNumber Of Chillers – The total number of chillers in the chiller plant. R: 0 to 8