ECG–UG–14-002 REVISION DATE PAGE30XAXWBACnet Option Rev G March 2017 15 OF 56Back to Beginning of Chapter – Table of Contents4.7 Objects listThe BACnet objects list includes the list of all objects names with respect to the followingparameters:AV Analogue ValueBV Binary ValueTL TREND_LOGCOV Change Of ValueIR Intrinsic Reporting (Alarming)CMD CommandableRO Read-Only Present Value (PV)RW Read/Write Present Value (PV)For BMS, the more often used objects are objects with names starting with GENUNIT, TEMP,PRESSURES, RUNTIMES and SETPOINT prefixes.Object NameTypeInstanceOptionCOVIncPVAccessDescriptionGENCONF_lead_cir AV 1 0 RO Cir Priority SequenceGENCONF_seq_typ BV 1 0 RO Staged Loading SequenceGENCONF_ramp_sel BV 2 0 RO Ramp Loading SelectGENCONF_off_on_d AV 2 0 RO Unit Off to On DelayGENCONF_nh_start AV 3 0 RO Night Mode Start HourGENCONF_nh_end AV 4 0 RO Night Mode End HourGENCONF_nh_limit AV 5 0 RO Night Capacity LimitGENCONF_bas_menu AV 6 0 RO Basic Menu ConfigurationGENCONF_lim_sel AV 7 0 RO Demand Limit Type SelectGENCONF_lim_mx AV 8 0 RO mA For 100% Demand LimitGENCONF_lim_ze AV 9 0 RO mA For 0% Demand LimitGENCONF_curr_sel BV 3 0 RO Current Limit SelectGENCONF_curr_ful AV 10 0 RO CurrentLimit at 100%GENCONF_free_dt AV 11 0 RO Free Cooling Delta T ThGENCONF_fc_tmout AV 12 0 RO Full Load TimeoutGENCONF_ice_cnfg BV 4 0 RO Ice Mode EnableGENCONF_al_rever BV 5 0 RO Reverse Alarms RelayPUMPCONF_hpumpseq AV 13 0 RO Condenser Pumps SequencePUMPCONF_cpumpseq AV 14 0 RO Cooler Pumps SequencePUMPCONF_pump_del AV 15 0 RO Pump Auto Rotation DelayPUMPCONF_pump_per BV 6 0 RO Pump Sticking ProtectionPUMPCONF_pump_sby BV 7 0 RO Stop Pump During StandbyPUMPCONF_pump_loc BV 8 0 RO Flow Checked If Pump OffPUMPCONF_stopheat BV 9 0 RO Cooler Pump Off In HeatPUMPCONF_stopcool BV 10 0 RO Cond Pump Off In CoolRESETCFG_cr_sel AV 16 0 RO Cooling Reset SelectRESETCFG_hr_sel AV 17 0 RO Heating Reset SelectRESETCFG_oat_crno AV 18 0 RO OAT No Reset ValueRESETCFG_oat_crfu AV 19 0 RO OAT Full Reset ValueRESETCFG_dt_cr_no AV 20 0 RO Delta T No Reset ValueRESETCFG_dt_cr_fu AV 21 0 RO Delta T Full Reset ValueRESETCFG_v_cr_no AV 22 0 RO Current No Reset Value