21Detailed cooling capacities* continuedNOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.* Detailed cooling capacities are based on indoor and outdoor unit at same elevation per ARI standard 210/240-94. If additional tubing length and/orindoor unit is located above outdoor unit, a slight variation in capacity may occur.† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27·C), deduct 835Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S)of indoor coil air per degree above 80°F (27°C).** System kW is total of indoor and outdoor unit kilowatts.†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.EWB – Entering Wet BulbEVAPORATORAIRCONDENSER ENTERING AIR TEMPERATURES °F85 95 105 115 125CFM EWBCapacityMBtuh† TotalSystemkW**CapacityMBtuh† TotalSystemkW**CapacityMBtuh† TotalSystemkW**CapacityMBtuh† TotalSystemkW**CapacityMBtuh† TotalSystemkW**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡38AYC060-33, 34 Outdoor Section With FB4BNB070 Indoor Section175072 65.6 32.7 5.42 63.2 32.0 6.00 60.5 31.0 6.64 57.4 29.9 7.31 54.1 28.8 8.0367 60.6 42.3 5.35 58.0 41.3 5.92 55.2 40.2 6.54 52.1 39.0 7.22 49.0 37.7 7.9363†† 56.3 41.1 5.31 53.7 40.0 5.87 51.1 38.9 6.47 48.3 37.6 7.12 45.0 36.2 7.8162 55.4 51.2 5.29 52.9 50.0 5.85 50.4 48.8 6.46 47.7 47.3 7.11 45.0 45.0 7.8057 53.9 53.9 5.27 52.0 52.0 5.83 49.8 49.8 6.44 47.6 47.6 7.10 44.9 44.9 7.80200072 66.2 34.0 5.54 63.9 33.4 6.12 61.0 32.4 6.75 58.0 31.4 7.43 54.5 30.2 8.1467 61.6 44.9 5.47 58.9 44.0 6.05 56.1 42.9 6.67 52.8 41.7 7.34 49.6 40.4 8.0663†† 57.4 43.8 5.43 54.6 42.6 5.99 51.8 41.4 6.60 49.0 40.2 7.25 45.7 38.8 7.9462 56.7 55.0 5.42 54.1 53.5 5.98 51.6 51.6 6.59 49.3 49.3 7.26 46.7 46.7 7.9857 56.0 56.0 5.42 53.9 53.9 5.98 51.6 51.6 6.59 49.3 49.3 7.26 46.7 46.7 7.97225072 66.2 35.0 5.64 64.3 34.7 6.24 61.0 33.5 6.85 58.1 32.6 7.53 54.6 31.3 8.2467 62.2 47.4 5.59 59.5 46.5 6.16 56.7 45.5 6.79 53.4 44.3 7.47 50.2 43.1 8.1863†† 58.2 46.3 5.55 55.2 45.0 6.12 52.4 43.8 6.72 49.5 42.6 7.38 46.3 41.2 8.0862 57.8 57.8 5.55 55.5 55.5 6.12 53.2 53.2 6.74 50.7 50.7 7.41 48.0 48.0 8.1357 57.7 57.7 5.56 55.4 55.4 6.12 53.1 53.1 6.74 50.6 50.6 7.41 48.1 48.1 8.13Multipliers for Determining the Performance With Other Indoor SectionsIndoorSection SizeCooling IndoorSection SizeCoolingCapacity Power Capacity PowerCC5A/CD5AA 060 0.95 0.99 CK5A/CK5BT 060 0.97 0.95CC5A/CD5AW 060 0.98 1.00 CK5A/CK5BX 060 0.97 0.93CE3AA 060 0.98 1.00 COILS + 58CV(A,X)135-22 FURNACECK3BA 060 0.95 0.97 CC5A/CD5AA 060 0.94 0.93CK5A/CK5BA 060 0.95 0.97 CC5A/CD5AW 060 0.97 0.94CK5A/CK5BT 060 0.95 0.97 CE3AA 060 0.97 0.94CK5A/CK5BX 060 0.98 0.99 CK3BA 060 0.97 0.96F(A,B)4BN(F,B,C) 060 0.97 1.01 CK5A/CK5BA 060 0.97 0.95FB4BNB 070 1.00 1.00 CK5A/CK5BT 060 0.97 0.95FC4CN(F,B) 060 0.97 1.02 CK5A/CK5BX 060 0.97 0.93FC4CNB 070 0.99 1.01 COILS + 58CV(A,X)155-22 FURNACEFG3AAA 060 0.96 0.99 CC5A/CD5AA 060 0.94 0.93FK4DNB 006 1.00 0.97 CC5A/CD5AW 060 0.97 0.94COILS + 58CV(A,X)110-22 FURNACE CE3AA 060 0.97 0.93CC5A/CD5AA 060 0.94 0.93 CK3BA 060 0.97 0.95CE3AA 060 0.97 0.93 CK5A/CK5BA 060 0.97 0.95CK3BA 060 0.97 0.95 CK5A/CK5BT 060 0.97 0.95CK5A/CK5BA 060 0.97 0.95 CK5A/CK5BX 060 0.97 0.92