Base unit dimensions — 50ZH060REQUIRED CLEARANCES TO COMBUSTIBLE MAT’LMillimeters (in.)Top of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0Side of Unit with Duct Openings . . . . . . . . . . . . . . . . . . . . . . 0Side of Unit Opposite Duct Openings . . . . . . . . . . . . . . . . . . . 0NEC REQUIRED CLEARANCESMillimeters (in.)Between Units, Power Entry Side . . . . . . . . . . . . . . . . . 1066.8 (42.00)Unit and Ungrounded Surfaces, Power Entry Side . . . . . . . 914.0 (36.00)Unit and Block or Concrete Walls and Other GroundedSurfaces, Power Entry Side . . . . . . . . . . . . . . . . . . . . 1066.8 (42.00)REQUIRED CLEARANCES FOR SERVICINGMillimeters (in.)Top of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 914.0 (36.00)Side of Unit Opposite Duct Openings . . . . . . . . . . . . . . . . 762.0 (30.00)Side of Unit with Power Entry . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)(Except for NEC Requirements)LEGENDNEC — National Electrical CodeNOTES:1. Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge. A removable fence or barricade requires no clearance.2. Dimensions are in millimeters. Dimensions in [ ] are in inches.3. is the center of gravity.UNITELECTRICALCHARACTERISTICSV-Ph-HzUNIT WEIGHT CENTER OF GRAVITY mm (in.)Lb Kg X Y Z50ZH060 208/230-1-60, 208/230-3-60,460-3-60 368 167 356 (14.00) 508 (20.00) 406 (16.00)7