Performance dataCOOLING CAPACITIES50ZH024 (2 TONS)Temp (F)Air EntOutdoorCoil(edb)Indoor Entering Air — CFM/BF700/0.12 800/0.14 900/0.15Indoor Entering Air — Ewb (F)72 67 63* 62 72 67 63* 62 72 67 63* 6285TC 26.6 24.1 22.2 22.0 27.0 24.5 22.6 22.4 27.3 24.9 23.0 22.8SHC 13.2 16.7 16.2 19.8 13.8 17.7 17.1 21.1 14.4 18.6 18.0 22.1kW 2.19 2.15 2.15 2.13 2.23 2.19 2.18 2.17 2.26 2.23 2.23 2.2195TC 25.6 23.0 21.2 20.9 26.0 22.8 21.6 21.4 26.3 23.8 21.8 21.7SHC 12.9 16.4 15.7 19.3 13.5 17.4 16.6 20.6 14.1 18.3 17.5 21.7kW 2.40 2.36 2.35 2.33 2.44 2.40 2.39 2.37 2.48 2.44 2.43 2.41105 TC 24.4 21.9 20.0 19.8 24.8 22.3 20.4 20.2 25.1 22.6 20.7 20.7SHC 12.5 15.9 15.2 18.8 13.1 16.9 16.2 20.0 13.7 17.9 17.0 20.7kW 2.64 2.60 2.57 2.56 2.69 2.64 2.62 2.60 2.73 2.68 2.66 2.65115 TC 23.2 20.6 18.7 18.5 23.5 21.0 19.0 19.1 23.8 21.3 19.3 19.7SHC 12.0 15.4 14.7 18.1 12.7 16.4 15.6 19.1 13.2 17.3 16.4 19.7kW 2.91 2.86 2.83 2.81 2.96 2.90 2.87 2.86 3.00 2.95 2.91 2.9150ZH030 (21⁄ 2 TONS)Temp (F)Air EntOutdoorCoil(edb)Indoor Entering Air — CFM/BF875/0.10 1000/0.11 1125/0.12Indoor Entering Air — Ewb (F)72 67 63* 62 72 67 63* 62 72 67 63* 6285TC 31.6 29.2 27.1 26.4 32.2 29.6 27.5 26.9 31.9 29.9 27.8 27.2SHC 15.0 19.8 19.5 23.9 15.7 20.9 20.7 25.4 15.9 22.0 21.7 26.6kW 2.80 2.76 2.73 2.71 2.87 2.82 2.79 2.77 2.90 2.88 2.84 2.8395TC 30.9 28.1 26.0 25.3 31.2 28.2 26.4 25.7 31.4 28.8 26.7 26.1SHC 15.0 19.4 19.1 23.4 15.6 20.6 20.3 24.9 16.1 21.7 21.3 26.0kW 3.05 3.00 2.96 2.94 3.11 3.05 3.02 3.00 3.16 3.11 3.07 3.06105TC 29.7 26.9 24.8 24.1 30.0 27.2 25.1 24.5 30.1 27.5 25.4 25.1SHC 14.6 19.0 18.6 22.8 15.2 20.2 19.8 24.2 15.7 21.4 20.9 25.1kW 3.31 3.26 3.21 3.19 3.37 3.32 3.27 3.26 3.41 3.37 3.34 3.33115TC 28.4 25.5 23.5 22.9 28.7 25.8 23.8 23.4 28.8 26.1 24.0 24.0SHC 14.2 18.6 18.1 22.2 14.9 19.8 19.2 23.4 15.4 20.9 20.3 24.0kW 3.58 3.53 3.46 3.44 3.64 3.60 3.53 3.51 3.69 3.65 3.59 3.59LEGENDBF — Bypass FactorEdb — Entering Dry-BulbEwb — Entering Wet-BulbkW — Total Unit Power InputLdb — Leaving Dry-BulbLwb — Leaving Wet-BulbSHC — Sensible Heat Capacity (1000 Btuh) NetTC — Total Capacity (1000 Btuh) Net*At 75 F entering dry bulb (Tennessee Valley Authority [TVA] ratingconditions); all others at 80 F entering dry bulb.NOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formulas may be used:sensible capacity (Btuh)tldb = tedb – 1.10 x cfmtlwb = Wet-bulb temperature corresponding to enthalpy of airleaving indoor coil (hlwb)total capacity (Btuh)hlwb = hewb – 4.5 x cfmWhere: hewb = Enthalpy of air entering evaporator coil3. The SHC is based on 80 F edb temperature of air entering evapo-rator coil.Below 80 F edb, subtract (corr factor x cfm) from SHC.Above 80 F edb, add (corr factor x cfm) to SHC.Correction Factor = 1.10 x (1 – BF) x (edb – 80).9