h. Blower will run for 90 seconds before beginning the callfor heat again.i. Furnace should ignite normally.Step 5—Checklist1. Put away tools and instruments. Clean up debris.2. Check that blower OFF-DELAY time is selected as desired.a. Verify that switches SW1-1 and SW1-6 are OFF and othersetup switches are set as desired. Verify that switchesSW1-7 and SW1-8 for the blower OFF DELAY are set asdesired.3. Verify that blower and burner access doors are properlyinstalled.4. Cycle test furnace with room thermostat.5. Check operation of accessories per manufacturer’s instruc-tions.6. Review User’s Guide with owner.7. Attach literature packet to furnace.SERVICE AND MAINTENANCE PROCEDURESThe ability to properly perform maintenance on this equip-ment requires certain knowledge, mechanical skills, tools, andequipment. If you do not possess these, do not attempt toperform any maintenance on this equipment other than thoseprocedures recommended in the User’s Manual. FAILURETO FOLLOW THIS WARNING COULD RESULT INPOSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUSPERSONAL INJURY, OR DEATH.ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARDFailure to follow safety warnings exactly, could result indangerous operation, serious injury, death or property dam-age.Improper servicing could result in dangerous operation,serious injury, death or property damage.-Before servicing, disconnect all electrical power to furnace.-When servicing controls, label all wires prior todisconnecting. Reconnect wires correctly.-Verify proper operation after servicing.Label all wires prior to disconnection when servicing con-trols. Wiring errors can cause improper and dangerousoperation.Step 1—IntroductionGENERALThese instructions are written as if the furnace is installed in anupflow application. An upflow furnace application is where theblower is located below the combustion and controls section of thefurnace, and conditioned air is discharged upward. Since thisfurnace can be installed in any of the 4 positions shown in Fig. 4,you must revise your orientation to component location accord-ingly.ELECTRICAL CONTROLS AND WIRINGThere may be more than 1 electrical supply to the unit. Checkaccessories and cooling unit for additional electrical supplies.The electrical ground and polarity for 115-v wiring must beproperly maintained. Refer to Fig. 22 for field wiring informationand to Fig. 51 for furnace wiring information.TABLE 11–(Tabulated Data Based On 21,000 Btuh High-Heat/14,500 Btuh for Low-Heat Per Burner,Derated 4 Percent For Each 1000 Ft Above Sea Level)ALTITUDERANGE(FT)AVG GASHEAT VALUEAT ALTITUDE(BTU/CU FT)SPECIFIC GRAVITY OF NATURAL GAS0.58 0.60 0.62 0.64OrificeNo.ManifoldPressureOrificeNo.ManifoldPressureOrificeNo.ManifoldPressureOrificeNo.ManifoldPressureU.S.A. Only9001to10,000600 46 3.6/1.7 46 3.7/1.8 46 3.8/1.8 45 3.7/1.8625 47 3.7/1.8 47 3.8/1.8 46 3.5/1.7 46 3.6/1.7650 47 3.4/1.6 47 3.6/1.7 47 3.7/1.8 47 3.8/1.8675 48 3.6/1.7 48 3.8/1.8 47 3.4/1.6 47 3.5/1.7700 48 3.4/1.6 48 3.5/1.7 48 3.6/1.7 48 3.7/1.8725 49 3.7/1.8 49 3.8/1.8 48 3.4/1.6 48 3.5/1.7* Orifice numbers 43 are factory installedFig. 49—Amp Draw Check With AmmeterA96316R Y W G10 TURNSTHERMOSTAT SUBBASETERMINALS WITHTHERMOSTAT REMOVED(ANITICIPATOR, CLOCK, ETC.,MUST BE OUT OF CIRCUIT.)HOOK-AROUNDAMMETEREXAMPLE: 5.0 AMPS ON AMMETER10 TURNS AROUND JAWS = 0.5 AMPS FOR THERMOSTATANTICIPATOR SETTINGFROM UNIT 24-VCONTROL TERMINALS37