2530WG + drycooler Minimum MaximumEvaporatorEntering water temperature at start-up °C 7.5* 27Leaving water temperature during operation °C 5** 20Entering/leaving water temperature difference K 2.5 7Condenser without hydronic kitEntering air temperature at start-up + duringoperation°C 10-15*** 40-45****Condenser with option 270V (kit with variable-speed pump)Entering air temperature at start-up+ duringoperation°C -10† 40-45***** For entering water temperatures below 7.5 °C at start-up, contact Carrier.** If the leaving water temperature is below 5 °C, a frost protection solution mustbe used. Please refer to option 6 for evaporator leaving water low-temperatureapplications (< 5 °C).*** The minimum entering air temperature is based on the drycooler selection.**** The maximum entering air temperature is based on the drycooler selection.† For applications with a low condenser entering air temperature the use of athree-way valve is recommended. This thre-way valve can be controlled by the0-10 V analogue output of the Pro-Dialog+ control.30WG Minimum MaximumEvaporatorEntering water temperature at start-up °C 7.5* 27Leaving water temperature during operation °C 5** 20Entering/leaving water temperature difference K 2.5 7CondenserEntering water temperature at start-up °C 15*** 55****Leaving water temperature during operation °C 20 60Entering/leaving water temperature difference K 2.5 18* For entering water temperatures below 7.5 °C at start-up, contact Carrier.** If the leaving water temperature is below 5 °C, a frost protection solution mustbe used. Please refer to option 6 for evaporator leaving water low-temperatureapplications (< 5 °C).*** For applications with a condenser entering temperature below 15 °C the use ofa three-way valve is recommended. This three-way valve can be controlled bythe 0-10 V analogue output of the Pro-Dialog+ control.**** For a water flow rate that corresponds to a maximum water-side temperaturedifference of 5 K.30WG + option 6 Minimum MaximumEvaporatorEntering water temperature at start-up °C -9.5* 27Leaving water temperature during operation °C -12* 20Entering/leaving water temperature difference K 2.5 3CondenserEntering water temperature at start-up °C 15** 55***Leaving water temperature during operation °C 20 60Entering/leaving water temperature difference K 2.5 18Note: Do not exceed the maximum operating temperature.* A frost protection solution must be used.** For applications with a condenser entering temperature below 15 °C the use ofa three-way valve is recommended. This three-way valve can be controlled bythe 0-10 V analogue output of the Pro-Dialog+ control.*** For a water flow rate that corresponds to a maximum water-side temperaturedifference of 5 K.5.2 - Operating range 61WGCondenser leaving water temperature, °CEvaporator leaving water temperature, °CEvaporator leaving water temperature, °CCondenser leaving water temperature, °C1520253035404550556065-8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20StandardOption 27261WG standard unit61WG unit with option 272 (brine to water)1520253035404550556065-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20StandardOption 65 - APPLICATION DATA5.1 - Operating limits 61WG61WG Minimum MaximumEvaporatorEntering water temperature at start-up °C 7.5* 27Leaving water temperature during operation °C 5** 20Entering/leaving water temperature difference K 2.5 7CondenserEntering water temperature at start-up °C 15*** 60****Leaving water temperature during operation °C 20 65Entering/leaving water temperature difference K 2.5 18* For entering water temperatures below 7.5 °C at start-up, contact Carrier.** If the leaving water temperature is below 5 °C, a frost protection solution mustbe used. Please refer to option 272 for evaporator leaving water low-temperatureapplications (< 5 °C).*** For applications with a condenser entering temperature below 15 °C the use ofa three-way valve is recommended. This three-way valve can be controlled bythe 0-10 V analogue output of the Pro-Dialog+ control.**** For a water flow rate that corresponds to a maximum water-side temperaturedifference of 5 K.61WG + option 272 (geothermal application) Minimum MaximumEvaporatorEntering water temperature at start-up °C -2.5* 25Leaving water temperature during operation °C -5* 20Entering/leaving water temperature difference K 2.5 5CondenserEntering water temperature at start-up °C 15** 60***Leaving water temperature during operation °C 20 65Entering/leaving water temperature difference K 2.5 18* A frost protection solution must be used.** For applications with a condenser entering temperature below 15 °C the use ofa three-way valve is recommended. This three-way valve can be controlled bythe 0-10 V analogue output of the Pro-Dialog+ control.*** For a water flow rate that corresponds to a maximum water-side temperaturedifference of 5 K.5.4 - Operating range 30WG30WG standard unit30WG unit with option 6 (brine)5.3 - Operating limits 30WG