17Table 5 — Blower Data — 50HQP072LEGEND NOTES:1. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C =High Rpm/Standard Motor.2. Unit factory shipped with standard static sheave and drive at 2.5 turnsopen. Other speed require field selection.3. For applications requiring higher static pressures, contact your local rep-resentative. Performance data does not include drive losses and is basedon sea level conditions.4. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 380Vfor 380/420V units.5. Airflow in l/s with wet coil and clean filter.AIRFLOW(l/s)EXTERNAL STATIC PRESSURE (Pa)0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375614BkW — — 0.09 0.12 0.14 0.17 0.19 0.21 0.24 0.25 0.27 0.29 0.31 0.32 0.34 0.35Sheave/Mtr — — B A A A A A C C C C C C C CRPM — — 505 563 615 655 695 730 765 790 815 840 870 890 910 925Turns Open — — 3 5 3.5 3 2 1 5 4.5 4 3.5 2.5 2.5 2 1.5661BkW — 0.12 0.14 0.17 0.19 0.22 0.24 0.26 0.29 0.30 0.33 0.34 0.36 0.38 0.40 —Sheave/Mtr — B A A A A C C C C C C C C C —RPM — 526 578 635 675 715 755 785 815 840 870 890 910 930 950 —Turns Open — 2 4.5 3 2.5 1.5 5 4.5 4 3.5 3 2 2 1.5 1 —708BkW 0.12 0.14 0.17 0.19 0.22 0.25 0.27 0.29 0.32 0.34 0.36 0.38 0.41 0.43 — —Sheave/Mtr B B A A A A C C C C C C C C — —RPM 500 547 604 650 695 735 775 805 835 865 890 915 940 960 — —Turns Open 3 1.5 4 3 2 1 4.5 4 3.5 3 2.5 2 1.5 1 — —755BkW 0.14 0.17 0.19 0.22 0.25 0.27 0.29 0.32 0.34 0.37 0.39 0.41 0.44 — — —Sheave/Mtr B B A A A A C C C C C C C — — —RPM 510 568 620 665 710 750 785 820 855 885 910 935 960 — — —Turns Open 2.5 1 3.5 2.5 1.5 1 4.5 3.5 3 2.5 2 1.5 1 — — —802BkW 0.16 0.19 0.22 0.24 0.27 0.29 0.32 0.34 0.36 0.39 0.42 0.44 — — — —Sheave/Mtr B A A A A C C C C C C C — — — —RPM 531 583 635 680 720 765 800 835 870 900 925 950 — — — —Turns Open 2 4.5 3.5 2.5 1.5 5 4 3.5 2.5 2 1.5 1 — — — —850BkW 0.15 0.18 0.21 0.24 0.26 0.29 0.31 0.34 0.36 0.39 0.42 0.45 — — — —Sheave/Mtr B B A A A A C C C C C C — — — —RPM 500 547 599 645 690 735 775 815 850 885 910 940 — — — —Turns Open 3 1.5 4 3 2 1 5 4 3 2.5 2 1.5 — — — —897BkW 0.18 0.21 0.23 0.27 0.30 0.33 0.36 0.40 0.43 0.46 0.49 0.52 — — — —Sheave/Mtr B B A A A A C C C C C C — — — —RPM 510 557 604 655 695 740 780 820 855 890 920 950 — — — —Turns Open 2.5 1.5 4 3 2 1 4.5 3.5 3 2 1.5 1 — — — —944BkW 0.21 0.23 0.26 0.29 0.33 0.37 0.41 0.44 0.48 0.50 0.54 0.56 — — — —Sheave/Mtr B B A A A C C C C C C C — — — —RPM 521 568 615 660 705 750 785 825 865 895 930 960 — — — —Turns Open 2.5 1 3.5 2.5 1.5 5.5 4.5 3.5 2.5 2 1.5 1 — — — —991BkW 0.25 0.28 0.32 0.34 0.37 0.40 0.44 0.48 0.52 0.55 0.58 — — — — —Sheave/Mtr B A A A A C C C C C C — — — — —RPM 536 583 630 670 715 755 795 835 875 905 940 — — — — —Turns Open 2 4.5 3.5 2.5 1.5 5 4 3.5 2.5 2 1 — — — — —1038BkW 0.28 0.30 0.34 0.37 0.41 0.45 0.48 0.52 0.56 0.59 0.62 — — — — —Sheave/Mtr A A A A A C C C C C C — — — — —RPM 557 599 645 685 730 770 810 850 885 915 950 — — — — —Turns Open 5 4 3 2 1 5 4 3 2.5 1.5 1 — — — — —1086BkW 0.32 0.35 0.38 0.42 0.45 0.48 0.52 0.56 0.60 0.63 0.67 — — — — —Sheave/Mtr A A A A A C C C C C C — — — — —RPM 573 620 660 705 745 785 820 860 895 925 960 — — — — —Turns Open 4.5 3.5 3 1.5 1 4.5 3.5 3 2 1.5 1 — — — — —1133BkW 0.36 0.39 0.43 0.46 0.49 0.54 0.58 0.62 0.65 0.69 — — — — — —Sheave/Mtr A A A A C C C C C C — — — — — —RPM 609 645 690 730 765 805 845 880 910 945 — — — — — —Turns Open 4 3 2.5 1.5 5 4 3 2.5 2 1 — — — — — —1180BkW 0.39 0.42 0.46 0.49 0.54 0.58 0.62 0.66 0.70 0.73 — — — — — —Sheave/Mtr A A A A C C C C C C — — — — — —RPM 620 660 700 740 780 815 850 885 920 950 — — — — — —Turns Open 3.5 3 2 1 4.5 4 3 2.5 1.5 1 — — — — — —— — Operation Not RecommendedBkW — Brake KilowattsESP — External Static PressureRPM — Revolutions Per MinuteA — Units with Standard Rpm/Standard Motor OptionB — Units with Low Rpm/Standard Motor OptionC — Units with High Rpm/Standard Motor Optiona50-8544