2350RHC,RVC048 — 1600 CFM NOMINAL AIRFLOWLEGEND*ARI 320 points (bold printing) are shown for comparison purposesonly. These are not certified data points.NOTES:1. Interpolation is permissible, extrapolation is not.2. All entering air conditions are 80 F db (dry bulb) and 67 F wb (wetbulb) in cooling and 70 F db in heating.3. All performance data is based upon the lower voltage of dual voltagerated units.4. See Performance Correction tables for operating conditions otherthan those listed above.5. Data table does not reflect ISO pump or fan corrections.6. Performance capacities shown in thousands of Btuh.EWT (F) GPM PRESSURE DROP COOLING HEATINGPSI Ft Wg TC TSC kW THR TC kW THA606.0 1.2 2.9 50.2 35.8 3.67 62.7 52.1 3.70 39.59.0 2.9 6.7 50.9 36.1 3.48 62.8 54.6 3.79 41.712.0 5.3 12.3 51.2 36.3 3.39 62.8 56.0 3.84 42.970*6.0 1.2 2.8 48.8 35.4 3.96 62.3 57.4 3.89 44.19.0 2.8 6.5 49.8 35.6 3.76 62.6 59.9 3.98 46.312.0 5.1 11.8 50.2 35.8 3.66 62.7 61.1 4.02 47.4806.0 1.2 2.7 46.6 34.8 4.25 61.1 62.0 4.05 48.29.0 2.7 6.3 48.2 35.3 4.05 62.0 64.2 4.13 50.112.0 5.0 11.5 48.8 35.4 3.95 62.3 65.2 4.16 51.085*6.0 1.2 2.7 45.2 34.3 4.38 60.2 64.0 4.12 49.99.0 2.7 6.2 47.1 34.9 4.20 61.4 66.0 4.18 51.712.0 4.9 11.3 47.9 35.2 4.10 61.8 66.9 4.21 52.6906.0 1.1 2.6 43.5 33.5 4.51 58.9 65.7 4.18 51.59.0 2.7 6.1 45.7 34.5 4.34 60.5 67.6 4.23 53.112.0 4.8 11.2 46.7 34.8 4.24 61.1 68.4 4.25 53.9956.0 1.1 2.6 41.6 32.6 4.62 57.4Operation Not Recommended9.0 2.6 6.1 44.1 33.8 4.47 59.312.0 4.8 11.0 45.2 34.3 4.38 60.2EWT — Entering Water Temperature (F)GPM — Gallons Per MinuteTC — Total Capacity (MBtuh)THA — Total Heat of Absorption (MBtuh)THR — Total Heat of Rejection (MBtuh)TSC — Total Sensible Capacity (MBtuh)