43APPENDIX A — WSHP OPEN SCREEN CONFIGURATIONLEGENDSCREEN NAME POINT NAME PASSWORDLEVEL EDITABLE RANGE DEFAULT NOTESEquipmentStatusOperating ModeNo PasswordRequiredOff, Fan Only, Economize,Cooling, Heating, Cont Fan,Test, Start Delay, DehumidifyDisplays unit operating modeSPT F Displays SPTSAT F Displays SATCondenser LeavingTemperature F Displays leaving condenserwater temperatureCondenser EnteringTemperature FDisplays entering condenserwater temperature (Valuewill not update when compressoris operating)FanOff/Low Speed/Medium SpeedHigh Speed/OnDisplays fan speed statusCompressor Capacity 0 - 100% Displays compressor capacityDamper Position 0 - 100%Displays current damper position(Viewable only if Ventilation DMPType = 2 position or DCV)H 2O Economizer 0 - 100% Displays position of economizer valveAuxiliary Heat 0 - 100%Displays position of auxiliaryreheat valve (Viewable only if LeavingAir Auxiliary Heat Type = 2 position,1 stage Elect or Modulating)Space RH 0 - 100% Displays space RH% (Viewable only ifHumidity Sensor = Installed)Dehumidification Inactive/Active Displays if dehumidification is active(Viewable only if FactoryDehumidification Reheat = Installed)IAQ CO 2 0 - 9999 ppm Displays the space CO 2 levelAlarm StatusSPT Alarm StatusNo PasswordRequiredNormal/Alarm Displays current spacetemperature conditionAlarming SPT F Displays the SPT thatexceeded the alarm limit (when SPTalarm above is in Alarm)SPT Alarm Limit F Displays the SPT alarm limit that wasexceeded; causing the alarm condition(when SPT alarm above is in Alarm)SPT Sensor AlarmStatus Normal/AlarmDisplays the status of the RnetSPT sensor - ALARM is displayedshould the sensor fail to communicatewith the control moduleIAQ Alarm Status Normal/Alarm Current IAQ/ventilation conditionCompressor AlarmStatus Normal/Alarm Current compressor conditionSAT Alarm Status Normal/Alarm Current SAT conditionCondensate OverflowAlarm Status Normal/Alarm Current status of the condensatedrain (overflow switch)Condenser Water Tem-perature Alarm Status Normal/Alarm Current status of thecondenser waterFilter Alarm Status Normal/Alarm Current filter conditionSpace RH Alarm Status Normal/Alarm Current space RH conditionOAT Alarm Status Normal/Alarm Current status of the OATbroadcast functionAirside Linkage Status Normal/Alarm Current linkage status if enabledCondenser WaterLinkage Normal/Alarm Current linkage status if enabledSensorCalibrationSATAdmin Passwordlevel access onlyF Display SATSAT Offset X -9.9 - 10.0 F 0 F Used to correct sensor readingLeaving CondenserWater Temperature F Displays Leaving CondenserWater TemperatureLeaving CW Offset X -9.9 - 10.0 F 0 F Used to correct sensor readingRnet SensorTemperature F Displays SPTRnet Offset X -9.9 - 10.0 F 0 F Used to correct sensor readingRH % Displays Space RH valueRH Sensor Offset X -15% - 15% 0 % Used to correct sensor reading°°°°°°°° °°° °°° °BAS — Building Automation SystemDCV — Demand Controlled VentilationIAQ — Indoor Air QualityOAT — Outdoor Air TemperatureRH — Relative HumiditySAT — Supply Air TemperatureSPT — Space TemperatureTPI — Third Party Integration