63When the ATTACH TO NETWORK DEVICE screen is ac-cessed, information can not be read from the ICVC on any de-vice (including the local chiller) until one of the devices listedon that screen is attached. The ICVC erases information aboutthe module to which it was attached to make room forinformation on another device. Therefore, a CCN module mustbe attached when this screen is entered.To attach any CCN device, highlight it using thesoftkey and press the softkey. The message “UP-LOADING TABLES, PLEASE WAIT” displays. The ICVCthen uploads the highlighted device or module. If the moduleaddress cannot be found, the message “COMMUNICATIONFAILURE” appears. The ICVC then reverts back to the AT-TACH TO DEVICE screen. Try another device or check theaddress of the device that would not attach. The upload processtime for each CCN module is different. In general, the upload-ing process takes 1 to 2 minutes. Before leaving the ATTACHTO NETWORK DEVICE screen, select the local device. Oth-erwise, the ICVC will be unable to display information on thelocal chiller.ATTACHING TO OTHER CCN MODULES — If thechiller ICVC has been connected to a CCN network or otherPIC controlled chillers through CCN wiring, the ICVC can beused to view or change parameters on the other controllers.Other PIC II chillers can be viewed and set points changed (ifthe other unit is in CCN control), if desired, from this particularICVC module.If the module number is not valid, the “COMMUNICA-TION FAILURE” message will show and a new address num-ber must be entered or the wiring checked. If the module iscommunicating properly, the “UPLOAD IN PROGRESS”message will flash and the new module can now be viewed.Whenever there is a question regarding which module onthe ICVC is currently being shown, check the device name de-scriptor on the upper left hand corner of the ICVC screen. SeeFig. 19.When the CCN device has been viewed, the ATTACH TONETWORK DEVICE table should be used to attach to the PICthat is on the chiller. Move to the ATTACH TO NETWORKDEVICE table (LOCAL should be highlighted) and pressthe softkey to upload the LOCAL device. TheICVC for the 19XR chiller will be uploaded and default screenwill display.NOTE: The ICVC will not automatically reattach to the localmodule on the chiller. Press the softkey to attach tothe LOCAL device and view the chiller operation.Service Operation — An overview of the tables andscreens available for the SERVICE function is shown inFig. 21.TO ACCESS THE SERVICE SCREENS — When theSERVICE screens are accessed, a password must be entered.1. From the main MENU screen, press thesoftkey. The softkeys now correspond to the numerals1, 2, 3, 4.2. Press the four digits of the password, one at a time. Anasterisk (*) appears as each digit is enteredNOTE: The initial factory-set password is 1-1-1-1. If thepassword is incorrect, an error message is displayedIf this occurs, return to Step 1 and try to access the SER-VICE screens again. If the password is correct, the soft-key labels change to:NOTE: The SERVICE screen password can be changedby entering the ICVC CONFIGURATION screen underSERVICE menu. The password is located at the bottomof the menu.The ICVC screen displays the following list of availableSERVICE screens:• Alarm History• Alert History• Control Test• Control Algorithm Status• Equipment Configuration• ISM (Starter) Config Data• Equipment Service• Time and Date• Attach to Network Device• Log Out of Device• ICVC ConfigurationSee Fig. 21 for additional screens and tables available fromthe SERVICE screens listed above. Use the softkey toreturn to the main MENU screen.NOTE: To prevent unauthorized persons from accessing theICVC service screens, the ICVC automatically signs off andpassword-protects itself if a key has not been pressed for 15minutes. The sequence is as follows. Fifteen minutes after thelast key is pressed, the default screen displays, the ICVCscreen light goes out (analogous to a screen saver), and theICVC logs out of the password-protected SERVICE menu.Other screen and menus, such as the STATUS screen can beaccessed without the password by pressing the appropriatesoftkey.TO LOG OUT OF NETWORK DEVICE — To access thisscreen and log out of a network device, from the default ICVCscreen, press the and softkeys. Enter thepassword and, from the SERVICE menu, highlight LOG OUTOF NETWORK DEVICE and press the softkey.The ICVC default screen will now be displayed.TIME BROADCAST ENABLE — The first displayed line,“Time Broadcast Enable,” in the SERVICE/EQUIPMENTCONFIGURATION/BRODEF screen, is used to designate thelocal chiller as the sole time broadcaster on a CCN network(there may only be one). If there is no CCN network presentand/or there is no designated time broadcaster on the network,current time and date, Daylight Saving Time (DST), andFig. 29 — Example of Attach to NetworkDevice ScreenSELECTATTACHATTACHATTACHSERVICEEXITMENU SERVICESELECT