134.3 - Electrical data, optional hydronic moduleThe pumps that are factory-installed in these units havemotors with efficiency class IE2. The additional electricaldata required* is as follows:motors of evaporator hydronic module pumps, 30Rw/30Rwa (option 116b)No.** Description*** 30RW/30RWA020 025 030 040 045 060 070 080 090 110 120 135 150 160 185 210 245 275 3001 Nominal efficiency at full load andnominal voltage% 77.4 77.4 77.4 77.4 77.4 81.3 81.3 81.3 81.3 83.2 83.2 83.2 86.1 86.1 86.1 86.1 86.1 86.1 86.11 Nominal efficiency at 75% rated loadand nominal voltage% 77.4 77.4 77.4 77.4 77.4 81.3 81.3 81.3 81.3 83.2 83.2 83.2 85.7 85.7 85.7 85.7 85.7 85.7 85.71 Nominal efficiency at 50% rated loadand nominal voltage% 76.0 76.0 76.0 76.0 76.0 80.0 80.0 80.0 80.0 81.0 81.0 81.0 81.0 84.3 84.3 84.3 84.3 84.3 84.32 Efficiency level IE23 Year of manufacture This information varies depending on the manufacturer and model at the time of incorporation. Please refer to themotor name plates.4 Manufacturer's name and trademark,commercial registration number andplace of manufacturer5 Product's model number6 Number of motor poles 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 27-1 Rated shaft power output at full loadand nominal voltage (400 V)kW 0.8 0.8 0.8 0.8 0.8 1.5 1.5 1.5 1.5 2.2 2.2 2.2 2.2 4.0 4.0 4.0 4.0 4.0 4.07-2 Maximum power input (400 V)**** kW 0.97 0.97 0.97 0.97 0.97 1.80 1.80 1.80 1.80 2.64 2.64 2.64 2.64 4.64 4.64 4.64 4.64 4.64 4.648 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 509-1 Rated voltage V 3 x 4009-2 Maximum current drawn (400 V)† A 1.9 1.9 1.9 1.9 1.9 3.7 3.7 3.7 3.7 5.2 5.2 5.2 5.2 7.7 7.7 7.7 7.7 7.7 7.710 Rated speed 48 r/s (2900 rpm)11 Product disassembly, recycling ordisposal at end of lifeDisassembly using standard tools. Disposal and recycling using an appropriate company.12 Operating conditions for which the motor is specifically designedI - Altitudes above sea level m < 1000††II - Ambient air temperature °C < 40IV - Maximum air temperature °C Please refer to the operating conditions given in this manual or in the specific conditions in the Carrier selectionprograms.V - Potentially explosive atmospheres Non-ATEX environmentmotors of evaporator hydronic module pumps, 30Rw/30Rwa (option 116C)No.** Description*** 30RW/30RWA060 070 080 090 110 120 135 150 160 185 210 245 275 3001 Nominal efficiency at full load and nominal voltage % 83.2 83.2 83.2 83.2 86.1 86.1 86.1 86.1 86.1 86.1 88.6 88.6 88.6 88.61 Nominal efficiency at 75% rated load and nominal voltage % 82.6 82.6 82.6 82.6 85.7 85.7 85.7 85.7 85.7 85.7 86.9 86.9 86.9 86.91 Nominal efficiency at 50% rated load and nominal voltage % 81.6 81.6 81.6 81.6 84.3 84.3 84.3 84.3 84.3 84.3 85.2 85.2 85.2 85.22 Efficiency level IE23 Year of manufacture This information varies depending on the manufacturer and model at the time ofincorporation. Please refer to the motor name plates.4 Manufacturer's name and trademark, commercial registrationnumber and place of manufacturer5 Product's model number6 Number of motor poles 2 2 2 2 2 2 2 2 2 2 2 2 2 27-1 Rated shaft power output at full load and nominal voltage (400 V) kW 2.2 2.2 2.2 2.2 4.0 4.0 4.0 4.0 4.0 4.0 5.5 5.5 5.5 5.57-2 Maximum power input (400 V)**** kW 2.64 2.64 2.64 2.64 4.64 4.64 4.64 4.64 4.64 4.64 6.2 6.2 6.2 6.28 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50 50 509-1 Rated voltage V 3 x 4009-2 Maximum current drawn (400 V)† A 4.5 4.5 4.5 4.5 7.7 7.7 7.7 7.7 7.7 7.7 10.2 10.2 10.2 10.210 Rated speed 48 r/s (2900 rpm)11 Product disassembly, recycling or disposal at end of life Disassembly using standard tools. Disposal and recycling using an appropriate company.12 Operating conditions for which the motor is specifically designedI - Altitudes above sea level m < 1000††II - Ambient air temperature °C < 40IV - Maximum air temperature °C Please refer to the operating conditions given in this manual or in the specific conditions inthe Carrier selection programs.V - Potentially explosive atmospheres Non-ATEX environment* Required by regulation 640/2009 with regard to the application of directive 2005/32/EC on the eco-design requirements for electric motors** Item number imposed by regulation 640/2009, annex I2b.*** Description given by regulation 640/2009, annex I2b.**** To obtain the maximum power input for a unit with hydronic module add the maximum unit power input from the electrical data table to the pump power input.† To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the electrical data table to the pump currentdraw.†† Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.