15Table 3 - Electrical data50RHE Power supply Voltage Compressor Fan Total Min. circuit Max.V-ph-Hz min./max. RLA LRA motor unit current fuse/HACRV FLA FLA A A006 220/240-1-50 197/254 2.3 15.0 0.4 2.7 3.2 15009 220/240-1-50 197/254 2.7 18.8 0.7 3.7 4.5 15012 220/240-1-50 197/254 3.9 22.2 0.7 4.5 5.6 15015 220/240-1-50 197/254 4.2 27.0 0.9 5.9 7.1 15019 220/240-1-50 197/254 6.8 45.0 0.9 8.6 10.5 15024 220/240-1-50 197/254 8.2 51.0 1.6 10.4 12.6 20030 220/240-1-50 197/254 9.1 54.0 1.7 11.2 13.6 20380-415-3-50 342/462 3.3 25.0 1.0 4.3 5.2 15036 220/240-1-50 197/254 11.5 83.0 2.7 17.2 20.8 35380-415-3-50 342/462 4.2 32.0 1.7 5.9 6.0 15042 380-415-3-50 342/462 5.5 34.5 1.7 6.0 7.1 15048 380-415-3-50 342/462 5.9 42.0 1.8 7.5 8.9 15060 380-415-3-50 342/462 8.2 61.8 2.5 9.9 11.8 15LegendFLA - Full load amperesHACR - Heating, air conditioning and refrigerationLRA - Locked rotor amperesRLA - Rated load amperes3.8.1 - Power connectionMake line voltage connection by connecting the incoming linevoltage wires to the L side of the CC terminal as shown in Fig. 13.See Table 3 for correct wire and maximum overcurrent protectionsizing.3.8.2 - Supply voltageOperating voltage to unit must be within voltage range indicatedon unit nameplate.On 3-phase units, voltages under load between phases must bebalanced within 2%. Use the following formula to determinethe percentage voltage imbalance:% voltage imbalance= 100 xExample: Supply voltage is 460-3-60.AB = 452 VoltsBC = 464 VoltsAC = 455 VoltsAverage voltage === 457Determine maximum deviation from average voltage:(AB) 457 - 452 = 5 V(BC) 464 - 457 = 7 V(AC) 457 - 455 = 2 VMaximum deviation is 7 V.Determine percent voltage imbalance.% voltage imbalance = 100 x= 1.53%max. voltage deviation from average voltageaverage voltage452 + 464 + 45537457This amount of phase imbalance is satisfactory as it is belowthe maximum allowable 2%.Operation on improper line voltage or excessive phase imbalanceconstitutes abuse and may cause damage to electrical components.NOTE: If more than 2% voltage imbalance is present, contactlocal electric utility.3.8.3 - 220-Volt operationAll 220-240-Volt units are factory wired for 208 Volts. The trans-formers may be switched to 220-Volt operation by switchingthe red (220-Volt) wire with the orange (240-Volt) wire at theTB1-1 terminal for single-phase and TB1-3 for 3-phase.Fig. 13 - 50RHE typical single-phase line voltagepower connection13713CapacitorCircuit breakerConnector CCUnit power supply. Seeelectrical data table forwire and breaker size.TransformerAquazone‘C’ controlLow voltageconnectorMotor