31Table 8 — Thermostat Control Input DisplayALARM RE-ALARM TIME — This decision is used to con-figure the number of minutes that will elapse betweenre-alarms. A re-alarm occurs when the condition that causedthe initial alarm continues to persist for the number of minutesspecified. Re-alarming continues to occur at the specifiedinterval until the alarm condition no longer exists.Re-Alarm Time: Display Units: MinutesDisplay Range: 0 to 1440Default Value: 0 (Disabled)CONTROL TEMPERATURE HYSTERESIS — This con-figuration defines the range above the high set point and belowthe low set point the space temperature must exceed for analarm condition to exist during occupied hours.For example, if the current setpoint is 75 F and the hystere-sis value is 5° F, an alarm will be generated if space tempera-ture exceeds the low limit of 70 F or the high limit of 80 F.ControlTemperatureHysteresis: Display Units: Delta Degrees F(Delta Degrees C)Range: 1.0 to 100.0Default Value: 5.0SUPPLY AIR TEMPERATURE — HIGH LIMIT — TheSupply Air Temperature High Limit alarm is used to monitorthe value of the supply air temperature within a specified range.If the supply air temperature becomes too high, an alarm condi-tion will exist.Supply AirTemperatureHigh Limit: Display Units: Degrees F (Degrees C)Display Range: –40.0 to 245.0Default Value: 150.0SUPPLY AIR TEMPERATURE — LOW LIMIT — TheSupply Air Temperature Low Limit alarm is used to monitorthe value of the supply air temperature within a specified range.If the supply air temperature becomes too low, an alarm condi-tion will exist.Supply AirTemperatureLow Limit: Display Units: Degrees F (Degrees C)Display Range: –40.0 to 245.0Default Value: 45.0INDOOR AIR QUALITY ALERT LIMIT — The Indoor-Air Quality Alert Limit alarm defines the allowable CO2 levelsduring occupied periods. If the CO2 levels become too low ortoo high during occupied periods, an alarm condition will exist.Indoor Air QualityLow Limit: Display Units: PPM (implied)Display Range: 0.0 to 5000.0Default Value: 0.0Indoor Air QualityHigh Limit: Display Units: PPM (implied)Display Range: 0.0 to 5000.0Default Value: 1200.0Table 9 — Alarm Service ConfigurationController Identification Screen — The controlleridentification screen contains reference information used toidentify the PremierLink™ controller. See Table 10.DESCRIPTION — The Description point displays the type ofdevice.LOCATION — The Location point shows the location of thedevice.SOFTWARE PART NUMBER — The Software Part Num-ber indicates the part number of the software being used.MODEL NUMBER — The Model Number indicates themodel number of the device being used.SERIAL NUMBER — The Serial Number indicates the serialnumber of the device being used.REFERENCE NUMBER — The Reference Number indi-cates the version of the software being used.Table 10 — Controller Identification*Software part number CESR131269-03 is version 1.2.Holiday Configuration Screen — The Holiday Con-figuration screen is used by the PremierLink controller to storeconfiguration fields for up to twelve holidays. See Table 11.START MONTH — The Start Month field is used to config-ure the month that the holiday will start. The numbers 1through 12 are used to indicate which month is specified.Start Month: Range: 1 to 12Default Value: 1 (January)START DAY — The Start Day field is used to determinewhich day the holiday will start.Start Day: Range: 1 to 31Default Value: 1DESCRIPTION VALUE UNITS STATUS FORCE NAMEY1 - Call for Cool 1 On Y1Y2 - Call for Cool 2 On Y2W1 - Call for Heat 1 Off W1W2 - Call for Heat 2 Off W2G - Call for Fan On GDESCRIPTION VALUE UNITS NAMEAlarm ControlAlarm Routing Control 00000000 ALRMCNTRealarm Time 0 min REALARMControl Temp Hysteresis 5.0 ^F SPTHYSSupply Air TemperatureLow Limit 45.0 dF LOWLIMHigh Limit 150.0 dF HIGHLIMIAQ High Alert LimitLow Limit 0.0 LOWLIMHigh Limit 1200.0 HIGHLIMDESCRIPTION VALUE UNITS NAMEDescription: Rooftop Control DevDescLocation: LocationSoftware Part Number: CESR131269-04* PartNumModel Number: ModelNumSerial Number: SerialNoReference Number: Version 1.3 RefNum