39Low Reference specifies Low Point of the Outdoor IAQSensor Range in ppm.Low Reference: Units: PPM (parts per million)Range: 0 to 5000Default Value: 0High Reference specifies High Point of the Outdoor IAQSensor Range in ppm.High Reference: Units: PPM (parts per million)Range: 0 to 5000Default Value: 2000OUTDOOR AIR QUALITY LOCKOUT POINT — Whenset to non-zero value, the IAQ algorithm will compare OutdoorIAQ reading against this decision and disable IAQ controlwhenever the value of OAQ exceeds this configured value.Outdoor AirQuality LockoutPoint: Range: 0 to 5000Default Value: 0SERVICE PASSWORD — The Service Password functiondefines the password needed to access the controller via theNavigator interface.Service Password: Range: 0000 to 9999Default Value: 1111PASSWORD ENABLE — The Password Enable function isused to require a password to be entered when attemptingto access the controller via the Navigator™ display moduleinterface.PasswordEnable: Range: Enable/DisableDefault Value: DisableMETRIC DISPLAY — The Metric Display function is usedto toggle the display for the Navigator between US and Metricunits.Metric Display: Range: On/OffDefault Value: OffOccupancy Maintenance Screen — The Occupan-cy Maintenance screen is used to check the occupied schedule.Information concerning the current occupied period is dis-played. See Table 16.MODE — The Mode point displays the current occupiedmode for the controller. If the controller is following its ownlocal schedule this is the result of the local schedule status. Ifthe controller is configured to follow a global schedule, thispoint displays the mode last received from a global schedulebroadcast.Mode: Display Range: 0 to 1Default Value: 0Network Access: NoneCURRENT OCCUPIED PERIOD — If the controller is con-figured to determine occupancy locally, the Current OccupiedPeriod point is used to display the current period determiningoccupancy.Current OccupiedPeriod: Display Range: 1 to 8Default Value: 0Network Access: NoneOVERRIDE IN PROGRESS — The Override in Progresspoint is used to display if an occupancy override is in progress.The point will display “Yes” if an override is in progress, or“No” if there is no override.Override InProgress: Display Range: Yes/NoDefault Value: NoNetwork Access: NoneOVERRIDE DURATION — The Override Duration pointdisplays the number of minutes remaining for an occupancyoverride which is in effect. If the override duration value down-loaded is in hours, the value will be converted to minutes. If theoccupancy schedule is occupied when override is initiated, thecurrent occupancy period will be extended by the number ofhours/minutes requested.If the current occupancy period is unoccupied when the oc-cupancy override is initiated, the mode will change to occupiedfor the duration of the number of hours/minutes downloaded. Ifthe occupancy override is due to end after the start of the nextoccupancy period, the mode will transition from occupancyoverride to occupied without becoming unoccupied, and theoccupancy override timer will be reset.OverrideDuration: Display Units: MinutesDisplay Range: 0 to 240Default Value: 0Network Access: NoneOCCUPIED START TIME — The Occupied Start Timepoint shows the time that the current occupied mode began. Ifthe current mode is unoccupied or the controller is following aglobal schedule, the value displayed by this point will remain atdefault.OccupiedStart Time: Display Range: 00:00 to 24:00Default Value: 00:00Network Access: NoneUNOCCUPIED START TIME — The Unoccupied StartTime point shows the time that the current occupied mode willend. This will also be the beginning of the next unoccupiedmode. If the current mode is unoccupied or the controller isfollowing a global schedule, the value displayed by this pointwill remain at default.UnoccupiedStart Time: Display Range: 00:00 to 24:00Default Value: 00:00Network Access: NoneNEXT OCCUPIED DAY — The Next Occupied Day pointdisplays the day of week when the next occupied period willbegin. This point is used with the Next Occupied Time so theuser will know when the next occupied period will occur. If thecontroller is following a global schedule this point will remainat default.Next OccupiedDay: Display Range: MON, TUE, WED,THU, FRI, SAT, SUNDefault Value: No display (Blank)Network Access: NoneNEXT OCCUPIED TIME — The Next Occupied Time pointdisplays the time day when the next occupied period willbegin. This point is used with the Next Occupied Day so theuser will know when the next occupied period will occur. If thePremierLink™ controller is following a global schedule thispoint will remain at default.Next OccupiedTime: Display Range: 00:00 to 24:00Default Value: 00:00Network Access: None