Start-up38 RTU OpenPoint Name/Description Default/RangeInput 2 Function D:– The type of sensor (4-20 mA) connected to terminals J4 – 1, 2, & 3.R:No SensorNo SensorIAQ SensorOAQ SensorSpace RH SensorInput 3 Function – The usage of Input 3. You must also set Input 3 Switch ConfigurationOptions:.No Function – The input is not used.Compressor Safety – Safety device status.Fan Status – Proves supply fan operation.Filter Status – Indicates a dirty filter.Remote Occupancy – Sets occupancy using a hardware contact.Door ContactD:– Sets occupancy using a hardware contact.R:Compressor SafetyNo FunctionCompressor SafetyFan StatusFilter StatusRemote OccupancyDoor ContactInput 3 Switch Configuration D:– The normal (de-energized) state for the set of contactsterminated at Input R:NONO/NC (normallyopen/normally closed)Input 5 Function – The usage of Input 5. You must also set Input 5 Switch ConfigurationOptions:.No Function – The input is not used.Fire Shutdown – Fire Safety device status. Inhibits operation when tripped.Fan Status – Proves supply fan operation.Filter Status – Indicates a dirty filter.Remote Occupancy – Sets occupancy using a hardware contact.Door ContactD:– Sets occupancy using a hardware contact.R:Fire ShutdownNo FunctionFire ShutdownFan StatusFilter StatusRemote OccupancyDoor ContactInput 5 Switch Configuration D:– The normal (de-energized) state for the set of contactsterminated at Input R:NCNO/NC (normallyopen/normally closed)Input 8 Function – The usage of Input 8. You must also set Input 8 Switch ConfigurationOptions:.No Function – The input is not used.Enthalpy Switch – Indicates enthalpy status (high or low).Fan Status – Proves supply fan operation.Filter Status – Indicates a dirty filter.Remote Occupancy – Sets occupancy using a hardware contact.Door ContactD:– Sets occupancy using a hardware contact.R:Enthalpy SwitchNo FunctionEnthalpy SwitchFan StatusFilter StatusRemote OccupancyDoor ContactInput 8 Switch Configuration D:– The normal (de-energized) state for the set of contactsterminated at Input R:NONO/NC (normallyopen/normally closed)Input 9 Function – The usage of Input 9. You must also set Input 9 Switch ConfigurationOptions:.No Function – The input is not used.Humidistat – Indicates high humidity condition.Fan Status – Proves supply fan operation.Filter Status – Indicates a dirty filter.Remote Occupancy – Sets occupancy using a hardware contact.Door ContactD:– Sets occupancy using a hardware contact.R:HumidistatNo FunctionHumidistatFan StatusFilter StatusRemote OccupancyDoor Contact