RTU Open 63DefaultRange: -40 to 245°FDemand LevelPoint Name/Description Occupied 1 2 3Occupied Cooling 1 – YellowThe space temperature must be greater than the Occupied Cooling 1 setpoint forthe VVT Master to consider the zone a cooling caller in a linked system. In a single-zone application, the cooling requirement begins as soon as the spacetemperature exceeds the Occupied Cooling setpoint. We recommend that theOccupied Cooling 1 value be set no less than 0.5°F above the Occupied Cooling75°Fsetpoint.76°F 77°F 79°FOccupied Cooling 2 – OrangeThe space temperature must be greater than the Occupied Cooling 2 setpoint togenerate a high space temperature alarm. We recommend that this value be setno less than 0.5°F above the Occupied Cooling 176°Fsetpoint.78°F 78°F 81°FUnoccupied SetpointsPoint Name/Description Default/RangeUnoccupied Heating D:– GrayThe heating setpoint the controller maintains while in unoccupied mode. R:55°F45 to 100°FUnoccupied Cooling D:– GrayThe cooling setpoint the controller maintains while in unoccupied mode. R:90°F-40 to 245°FUnoccupied Heating 1 – Light BlueThe space temperature must be less than the Unoccupied Heating 1 setpoint for the VVTMaster to consider the zone an unoccupied heating caller in a linked system. In a single-zoneapplication, the unoccupied heating requirement begins as soon as the space temperature fallsbelow the Unoccupied Heating setpoint. We recommend that the Unoccupied Heating 1 valuebe set no less than 0.5°F below the Unoccupied HeatingD:setpoint.R:54°F-40 to 245°FUnoccupied Heating 2 – Dark BlueThe space temperature must be less than the Unoccupied Heating 2 setpoint to generate anunoccupied low space temperature alarm. We recommend that this value be set no less than0.5°F below the Unoccupied Heating 1D:setpoint.R:52°F-40 to 245°FUnoccupied Cooling 1 – YellowThe space temperature must be greater than the Unoccupied Cooling 1 setpoint for the VVTMaster to consider the zone an unoccupied cooling caller in a linked system. In a single-zoneapplication, the unoccupied cooling requirement begins as soon as the space temperatureexceeds the Unoccupied Cooling setpoint. We recommend that the Unoccupied Cooling 1 valuebe set no less than 0.5°F above the Unoccupied CoolingD:setpoint.R:91°F-40 to 245°FUnoccupied Cooling 2 – OrangeThe space temperature must be greater than the Unoccupied Cooling 2 setpoint to generate anunoccupied high space temperature alarm. We recommend that this value be set no less than0.5°F above the Unoccupied Cooling 1D:setpoint.R:93°F-40 to 245°F