VVT Zone Controller 51NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. Youmust enter an integer only.Statusi-Vu / Field Assistant:Navigation:BACview:Properties > Equipment > StatusHOME > STATUSPoint Name/Description RangeTerminal Mode R:– The controller's current operating status. OFFHEATINGWARM-UPVENTCOOLINGDEHUMIDFYREHEATPRESSURIZEEVACUATESHUTDOWNIAQ OVERRIDEAIR BALANCINGTerm Type R:– The type of zone terminal that the controller is installed on. Single DuctParallel FanSeries FanSpace Temperature - Prime Variable R:– The space temperature value currently used forcontrol.-56 to 245°FDamper Position R:– The current damper position. 0 to 100%Supply Air Temperature R:– The current supply air temperature. -56 to 245°FHeating Capacity R:– The current reheat capacity when the zone is configured for reheat. 0 to 100%Baseboard Heating Capacity R:– The current modulating baseboard heat capacity whenthe zone is configured for Combination Baseboard and Ducted Heat.0 to 100%Outdoor Air Temperature R:– The current outdoor air temperature from a linked airsource, if available, or from another network source.-56 to 245°FFan – The status of the terminal fan if Term Type is Parallel Fan or Series Fan R:. On/OffCO2 (ppm) – The current IAQ value if Optional Sensor Type is set to IAQ Control R:. 0 to 5000ppmSpace Relative Humidity – The current space relative humidity if Optional Sensor Typeis set to RH ControlR:.0 to 100%rhShutdown – When Active D:, disables all control functions, at normal equipment timedelays and close the damper. R:InactiveInactive/ActiveAppendix A: VVT Zone Controller Points/Properties