SiBE28-805 Troubleshooting (OP: Central Remote Controller)Troubleshooting 2154.3 “MA” Improper Combination of Optional Controllers forCentralized ControlRemoteControllerDisplayMAApplicableModelsCentral remote controller intelligent Touch ControllerSchedule timerMethod ofMalfunctionDetectionDetect the malfunction according to DIII-NET transmission data.MalfunctionDecisionConditionsWhen the schedule timer is set to individual use mode, other central component is present.When multiple master controller are present.When the remote control adaptor is present.SupposedCauses Improper combination of optional controllers for centralized control More than one master controller is connected Defect of PC board of optional controller for centralized control