SiBE28-805 Outline of Control (Indoor Unit)Function 61(2) The heater control (ON/OFF)is conducted by convertingthe heater temperature intothe condensing pressureequivalent saturatedtemperature (Tc) accordingto the temperature detectionthrough the high pressure sensor (SINPH) of the outdoor unit.[Fan residual operation]While the heater turns OFF, in order to prevent the activation of the thermal protector, the fanconducts residual operation for a given period of time after the heater turns OFF. (Thisoperation is conducted regardless of with or without heater equipped.)Residual operation time = 100 seconds on ceiling suspended type or 60 seconds on other types6.10 List of Swing Flap OperationsSwing flaps operate as shown in table below.*1. L or LL only on FMCQ modelsON 50ºC 60ºCOFFCondensing pressureequivalent saturatedtemperatureFan FlapFMCQHeatingHot start from defrostingoperationSwing OFF HorizontalWind direction set OFF HorizontalDefrosting operationSwing OFF HorizontalWind direction set OFF HorizontalThermostat OFFSwing LL HorizontalWind direction set LL HorizontalHot start from thermostatOFF mode (for preventionof cold air)Swing LL HorizontalWind direction set LL HorizontalStopSwing OFF HorizontalWind direction set OFF HorizontalCoolingThermostat ON in dryoperation using microcomputerSwing L*1 SwingWind direction set L*1 SetThermostat OFF in dryoperation using microcomputerSwingOFF or LSwingWind direction set Horizontal or SetThermostat OFF incoolingSwing Set SwingWind direction set Set SetStopSwing OFF HorizontalWind direction set OFF HorizontalMicro computer control(including coolingoperation)Swing L SwingWind direction set L Set