Outdoor Air Fan Set-UpTable 30: Outdoor Air Fan Set Up Menu OA Fan1 Spd is a status only item that displays the currentspeed of outdoor fan 1 in percent of maximum speedOA Fan1 Cmd= is is a status only item that indicates thecurrent command speed of outdoor fan 1OA Fan1 Amps is a status only item which displays the currentamperage being drawn by outdoor fan 1OA Fan2 Spd is a status only item that displays the currentspeed of outdoor fan 2 in percent of maximum speedOA Fan2 Cmd= is is a status only item that indicates thecurrent command speed of outdoor fan 2OA Fan2 Amps is a status only item which displays the currentamperage being drawn by outdoor fan 2PTD is a status only item which displays the current dischargerefrigerant line pressure sensor readingPTS is a status only item which displays the current suctionrefrigerant line pressure sensor readingDisch Sat Tmp is a status only item which displays the currentdischarge pressure equivalent saturation temperatureEffDshSatTSpt is a status only item which displays theeffective discharge saturation temperature set point used tocontrol the outdoor air fans in the cooling mode of operationOA Temp is a status only item which displays the currenttemperature reading from the unit mounted outdoor airtemperature sensorINV Fin Temp is a status only item which displays the currentinverter compressor control board cooling fin temperature.This value is used in the inverter compressor fin temperaturelimiting protection functionDischSatTDiff is an adjustable item which sets a differentialabove the current outdoor air temperature reading which isused to establish the EffDshSatTSptDischSatTDB is an adjustable item which sets a controldeadband around the EffDshSatTSptItem Display Name DefaultSetting Range PasswordLevelOA Fan StatusOA Fan1 Spd= — 0–100% 4OA Fan1 Cmd= — 0-100% 4OAFan1 Amps= — 0–50A 4OA Fan2 Spd= — 0–100% 4OA Fan2 Cmd= — 0-100% 4OAFan2 Amps= — 0–50A 4Refrig Circuit StatusPTD= — 0–5000kPa 4PTS= — 0–5000kPa 4Disch Sat Tmp= — -50 0–212 0°F 4EH DshSatTSpt= — -50 0–212 0°F 2OA Temp= — -50 0–200 0°F 4INV Fin Temp= — -50 0–200 0°F 2OA Fan Set UpDischSatTDiff= 15°F 10 0–50 0°F 2DischSatTDB= 2 0°F 0–10 0°F 2OA Fan Period= 10s 0–999s 2OA Fan Gain= 2 0 0–100 2OA Fan PAT= 20s 0–999s 2IFB Comm StatusIFB SWVersion= — V0222013 2IFBCommStatus= —OK2OF2ErrOF1ErrOF12ErrINVErrACS3ErrACS1ErrACS13ErrInit3ErrInit1ErrInit13ErrIFBRstMBErrPrvCommStatus — Same as IFBCommStatus 2MM/DD/YY HH:MM:SS — — 2ACS1 DataRcvd= —ErrAll2F1F2ErrINVF2ErrF2ErrINVF1ErrF1ErrINVErrAllOKACS3 DataRcd= — Error 2OKFault Code Details (Active Fault Codes)INVAlarmCode= — 2 digit alpha-numeric 2Code Text — String 2OF1AlarmCode= — 2 digit alpha-numeric 2Code Text — String 2OF2AlarmCode= — 2 digit alpha-numeric 2Code Text — String 2Fault Code Details (Previous Fault Codes)PrvINVAlmCode= — 2 digit alpha-numeric 2Code Text — String 2MM/DD/YY HH:MM:SS — — 2PrvOF1AlmCode= — 2 digit alpha-numeric 2Code Text — String 2MM/DD/YY HH:MM:SS — — 2PrvOF2AlmCode= — 2 digit alpha-numeric 2Code Text — String 2MM/DD/YY HH:MM:SS — — 2coMMIssIon unItwww DaikinApplied com51 OM 1141-3 • MICROTECH UNIT CONTROLLER