English5The indoor unit must be installed in such a way so as to preventshort circuit of the cool discharged air with the hot return air.Please follow the installation clearance shown in the figure. Donot place the indoor unit where there could be direct sunlightshining on it. Also, this location must be suitable for pipingand drainage, and be away from doors or windows.min. 50(Space formaintenance)Air flow(Indoor)The refrigerant piping can be routed to the unit in a number ofways (left or right from the back of the unit), by using the cut-out holes on the casing of the unit (see figure). Bend the pipescarefully to the required position in order to align it with theholes. For the side and bottom, hold the bottom of the pipingand then position it to the required direction (see figure). Thecondensation drain hose can be taped to the pipes.Right-side, right-back or right-bottom pipingmin. 50(Space formaintenance)min. 30(Space forperformance)Required spaceRight-back pipingBind coolant pipeand drain hosetogether withinsulating tape.All dimensions are in mmRight-bottompipingRemove pipe port coverhere for right-bottom pipingRight-sidepipingRemove pipe port coverhere for right-side pipingRemove pipe port cover here forleft-bottom pipingRemove pipe portcover here forleft-side pipingLeft-backpipingLeft-sidepipingLeft-bottom pipingLeft-side, left-back or left-bottom pipingINSTALLATION OF THE INDOOR UNIT