SiBE041029EB Forced Cooling OperationTrial Operation and Field Settings 1042. Forced Cooling OperationIndoor UnitOutdoor Unit: RX50/60G2V1B, 71 class∗ The illustration is for 71 class as representative.Outdoor Unit: RX50/60G3V1BCaution When pressing the button, do not touch the terminal board. It has a high voltage and may causeelectric shock.Item Forced CoolingConditions The forced cooling operation is allowed when both of the following conditions aremet.1) The outdoor unit is not abnormal and not in the 3-minute standby mode.2) The outdoor unit is not operating.Start The forced cooling operation starts when any of the following conditions are fulfilled.1) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit for 5seconds.2) Press the forced cooling operation ON/OFF button (SW1) on the outdoor unitwithin around 3 minutes after power is supplied.Commandfrequency 50/60 class: 66 Hz71 class: 31 HzEnd The forced cooling operation ends when any of the following conditions are fulfilled.1) The operation ends automatically after 15 minutes.2) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit again.3) Press the ON/OFF button on the remote controller.4) Press the forced cooling operation ON/OFF button (SW1) on the outdoor unit.Others Protection functions have priority over all other functions during forced coolingoperation.Indoor unit ON/OFF button(R19650)LED-ASW4ONA B C DS102SW1S2Forced cooling operationON/OFF button (R19531)1 2 3Screwdriver (R19532)Forced cooling operationON/OFF button (SW1)Push