SiBE041434E Main FunctionsFunction and Control 221.6 Automatic OperationOutline Automatic Cooling / Heating FunctionWhen the automatic operation is selected with the remote controller, the microcomputerautomatically determines the operation mode as cooling or heating according to the roomtemperature and the set temperature at start-up.The unit automatically switches the operation mode to maintain the room temperature at the settemperature.Detail Ts: set temperature (set by remote controller)Tt: target temperature (determined by microcomputer)Tr: room thermistor temperature (detected by room temperature thermistor)C: correction value1. The set temperature (Ts) determines the target temperature (Tt).(Ts = 18 ~ 30°C).2. The target temperature (Tt) is calculated as;Tt = Ts + Cwhere C is the correction value.C = 0°C3. Thermostat ON/OFF point and operation mode switching point are as follows.Tr means the room thermistor temperature.(1) Heating → Cooling switching point:Tr ≥ Tt + 2.5°C (20/25 class)Tr ≥ Tt + 3.0°C (35/42/50 class)(2) Cooling → Heating switching point:Tr < Tt – 2.5°C(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heatingoperation.4. During initial operationTr ≥ Ts : Cooling operationTr < Ts : Heating operation20/25 classEx: When the target temperature is 25°CCooling → 23°C: Thermostat OFF → 22°C: Switch to heatingHeating → 26.5°C: Thermostat OFF → 27.5°C: Switch to cooling35/42/50 classEx: When the target temperature is 25°CCooling → 23°C: Thermostat OFF → 22°C: Switch to heatingHeating → 27°C: Thermostat OFF → 28°C: Switch to cooling(R11893)Target temperature + 2.5˚CHeating OperationTarget temperature – 2.5˚CCooling OperationTarget temperature – 2.0˚C= Thermostat OFFTarget temperature + 1.5˚C= Thermostat OFFTarget temperature + 3.0˚CHeating OperationTarget temperature – 2.5˚CCooling Operation(R11892)Target temperature – 2.0˚C= Thermostat OFFTarget temperature + 2.0˚C= Thermostat OFF