Outdoor Unit - RXG50K2V1B SiBE061121215 Removal Procedure3.7 Removal of Outdoor Electronic Expansion ValveProcedure Warning Be sure to wait for 10 minutes or more after turning off all powersupplies before disassembling work.Step Procedure Points1 Pull out the outdoorelectronic expansionvalve coil.2 Remove the sheets ofputty.WarningBe careful not to get yourselfburnt with the pipes and otherparts that are heated by thegas brazing machine.WarningIf the refrigerant gas leaksduring work, ventilate theroom. (If the refrigerant gas isexposed to flames, toxic gasmay be generated.)CautionFrom the viewpoint of globalenvironment protection, donot discharge the refrigerantgas in the atmosphere. Makesure to collect all therefrigerant gas. Before working, makesure that the refrigerantgas is empty in the circuit. Be sure to apply nitrogenreplacement whenheating up the brazedpart.3 Heat up the 2 brazedparts of the outdoorelectronic expansionvalve and remove it.Outdoor electronic expansion valve coil(R15369)Outdoor electronic expansion valve(R15370)