4-134.8 Parts ReplacementAfter replacing parts, check that the parts areable to operate correctly.4.8.1 CompressorPreparation for installing a new compressor1. Check the replacement compressor andaccessories.Identification plate is affixed on the replacementcompressor.Check the unit model according tothe identification plate.Fig. 1 Replacement compressorWeight 40kgRefrigerant oil DAPHNE FVC68D charged.Dry nitrogen gas charged.Suction pipe receptacle(with a blind cap)Discharge pipe receptacle(with a blind cap)Injection pipe receptacle(with a blind cap)Identification plateTerminalboxCompressor identification plateAccessoriesPacking for suction/ discharge 2 pcs.pipe receptacles2. Remove the blind caps fromthe discharge, suction andinjection pipe receptacles.Compressor removal1. Remove the compressor cover (Fig. 2).2. Disconnect the compressor cable from theterminal box.3.Disconnect three connecting pipes(Discharge, suction and injection pipes)Note 1. When removing pipes, use two wrenchesso as not to damage the pipes (Figs. 3 & 4).Note 2. After disconnecting the discharge andsuction pipes, also remove the packing(Fig. 3).4. Remove the one bolt that holds the compressortop and the four bolts that hold the compressorbase.36272622Fig.4Fig.3Suction pipeDischarge pipe(Lock nut connection)PackingLock nutInjection pipe(Flare nut connection)Two wrenchesTwo wrenchesRotateRotateHold onHold onRemoval of thecompressor coverFig.2https://daikin-p.ru