SiUS371614E Field Setting from Remote ControllerField Settings 1181.4 Setting Contents and Code No. for Indoor Units : Factory settingModeNo.(∗2)FirstCodeNo.Setting ContentsSecond Code No.01 02 03 0410(20)0Filter sign setting(Setting for display time toclean air filter)(Sets display time to clean airfilter to half when there isheavy filter contamination.)Ultra long lifefilterLightApprox.10,000hrs.HeavyApprox.5,000hrs.— —Long life filterApprox.2,500hrs.Approx.1,250hrs.StandardfilterApprox.200 hrs.Approx.100 hrs.1 Ultra long life filter sign setting Long life filter Ultra long life filter — —1 (∗7) Filter cleaning sign time (Light/Heavy) 2,500/1,250 10,000/5,000 — —2 Selection of thermistorRemote controller +Suction airthermistorOnly suction airthermistorOnly remotecontrollerthermistor —2 (∗6) Remote sensor and remote controller thermistor — Only remote sensorOnly remotecontrollerthermistor —3 Filter cleaning sign Displayed Not displayed — —6 Remote controller thermostat control during thegroup controlRemote controllerthermostat controlis not permittedRemote controllerthermostat controlis permitted— —7 (∗9) Time for absence area detection 30 minutes 60 minutes — —11(21)1 Auxiliary electric heater ON temperature: Ton Refer to page 124 for detail.2 Auxiliary electric heater OFF temperature: Toff3 Setting the airflow rate when heating Standard Slightly increased Increased —3 (∗6) Electric heater setting Refer to page 125 for details.5 (∗6) Electric heater capacity setting Refer to page 125 for details.6 (∗9) Setting the rate of human detection High sensitivity Low sensitivity StandardsensitivityInfraredpresence/floorsensordisabled7 Airflow adjustment OFF Completion ofairflow adjustmentStart of airflowadjustment —8 (∗9) Compensating the temperature around people Suction airtemperature onlyPriorities given onthe suction airtemperatureStandardPriorities givenon the floortemperature9 (∗9) Compensating the floor temperature –4°C (–7.2°F) –2°C (–3.6°F) 0°C (0°F) +2°C (+3.6°F)12(22)0 Optional output switching(field selection of output for adaptor for wiring) Refer to page 127 for detail.1External ON/OFF input(Set when ON/OFF is to be controlled fromoutside.)Refer to page 127 for detail.2 Thermostat switching(Set when remote sensor is to be used) 1°C (1.8°F) 0.5°C (0.9°F) — —3 Airflow setting when heating thermostat is OFF LL tap Set fan speed OFF (∗8) —4Setting of operation mode to AUTO(automatic temperature differential setting forVRV system Heat Recovery series cool/heat) Refer to page 128 for detail.5 Auto restart after power failure reset Not equipped Equipped — —6 Airflow setting when cooling thermostat is OFF LL tap Set fan speed OFF (∗8) —