SiUS371614E Field Setting from Remote ControllerField Settings 1341.4.3 Outdoor-Air Processing Unit - Field Setting (Remote Controller): Factory setting+: The same value continues.1.4.4 Setting of Operation Control Mode from Remote Controller(Field Setting)The operation control mode is compatible with a variety of controls and operations by limiting the functions of theoperation remote controller. Furthermore, operations such as remote controller ON/OFF can be limited inaccordance with the combination conditions. (Refer to information in the next page.)Central remote controller is normally available for operations. (Except when centralized monitor is connected)1.4.5 Contents of Control Modes20 modes consisting of combinations of the following 5 operation modes with temperature and operation modesetting by remote controller can be set and displayed by operation modes 0 through 19. ON/OFF control impossible by remote controllerUsed when you want to turn ON/OFF by central remote controller only.(Cannot be turned ON/OFF by remote controller.) OFF control only possible by remote controllerUsed when you want to turn ON by central remote controller only, and OFF by remote controller only. CentralizedUsed when you want to turn ON by central remote controller only, and turn ON/OFF freely by remotecontroller during set time. IndividualUsed when you want to turn ON/OFF by both central remote controller and remote controller. Timer operation possible by remote controllerUsed when you want to turn ON/OFF by remote controller during set time and you do not want to startoperation by central remote controller when time of system start is programmed.ModeNo.FirstCodeNo. Setting Contents Second Code No.01 02 03 04 05 06 07 08 09 10 11 12 13 14 1510(20)0 Filter contamination 2500 hr 1250 hr — — — — — — — — — — — — —3 Display time toclean air filtercalculation Display Nodisplay — — — — — — — — — — — — —12(22)1 External ON/OFFinputForcedOFF ON/OFFcontrol — — — — — — — — — — — — —5 Power failureautomatic reset Notequipped Equipped — — — — — — — — — — — — —14(24)3Dischargepipetemperature(cooling)°C 13 14 15 16 17 18 19 20 21 22 23 24 25+ 25+ 25+°F 55.4 57.2 59 60.8 62.6 64.4 66.2 68 69.8 71.6 73.4 75.2 77+ 77+ 77+4Dischargepipetemperature(heating)°C 18 19 20 21 22 23 24 25 26 27 28 29 30+ 30+ 30+°F 64.4 66.2 68 69.8 71.6 73.4 75.2 77 78.8 80.6 82.4 84.2 86+ 86+ 86+