• Outdoor Unit • RZAG-LV12• Split - Sky Air • RZAG-LV142 SpecificationsTBivalent Tbiv(bivalenttemperature)°C -7 -Pdh(declaredheatingcap)kW 5.00 8.08 8.42 -COPd (declaredCOP)2.50 2.93 2.85 -PowerinputkW 2.00 2.76 2.95 -ACondition(-7°C)Pdh(declaredheatingcap)kW 5.00 8.08 8.42 -COPd (declaredCOP)2.50 2.93 2.85 -PowerinputkW 2.00 2.76 2.95 -BCondition(2°C)Pdh(declaredheatingcap)kW 3.04 5.06 5.13 -COPd (declaredCOP)4.70 4.76 4.74 -PowerinputkW 0.65 1.06 1.08 -CCondition(7°C)Pdh(declaredheatingcap)kW 2.63 4.38 3.95 -COPd (declaredCOP)6.41 6.12 5.97 -PowerinputkW 0.41 0.72 0.66 -DCondition(12°C)Pdh(declaredheatingcap)kW 2.77 4.85 4.20 -COPd (declaredCOP)7.39 7.57 7.50 -PowerinputkW 0.37 0.64 0.56 -Pto (Thermostat off) W 8.0 11.0 -Cooling Psb (Standby mode cooling) W 9.0 10.0 -Cdc (Degradation cooling) 0.25 -Heating Psb (Standby mode heating) W 9.0 10.0 -Cdh (Degradation heating) 0.25 -Pck (Crankcase heater mode) W 0.0 -Poff (Off mode) W 0.0 -Cooling function included Yes -Heating function included Yes -Average climate included Yes -Cold season included No -Warm season included No -Ecolabel logo No -Eurovent Sound power leveloutdoorCooling Nom. dBA 64 66 -Sound power levelindoorCooling Nom. dBA 53 61 -2-1 Capacity and Power input FCAHG71F/RZAG71LV1FCAHG100F/RZAG100LV1FCAHG125F/RZAG125LV1FCAHG140F/RZAG140LV1