Troubleshooting for Outdoor Unit SiBE121135_A215 Service Diagnosis7.12 High Pressure Control in CoolingError Code F6Outdoor Unit LEDDisplayA j 1 i 2 h 3 i 4 i 5 h∗ LED5 is equipped only on the 5-room model.Method of ErrorDetectionHigh-pressure control (operation halt, frequency drop, etc.) is activated in cooling mode if thetemperature sensed by the outdoor heat exchanger thermistor exceeds the limit.Error DecisionConditions The temperature sensed by the outdoor heat exchanger thermistor rises above about 65°C. The error is cleared when the temperature drops below about 50 °C.SupposedCauses The installation space is not large enough. Dirty outdoor heat exchanger Defective outdoor fan motor Defective stop valve Defective outdoor electronic expansion valve or coil Defective outdoor heat exchanger thermistor Defective outdoor unit PCBTroubleshootingCheck No.01Refer to P.230Check No.12Refer to P.234Check No.17Refer to P.238Check No.18Refer to P.238Check No.19Refer to P.239(R14413)CautionReplace the fan motor.Reconnect the connector orfan motor lead wires.Replace the stop valve.Replace the outdoor heatexchanger thermistor.Replace the outdoor unitPCB.Replace the outdoorelectronic expansion valveor the coil.Replace the outdoor unitPCB.Change the installationlocation or direction.Clean the outdoor heatexchanger.Check the installation space.NGOKOKNGNGOKOKOKNGNGCheck No. 19Check the outdoor fan.Check No. 18Check the dischargepressure.Check No. 12Check the outdoor electronicexpansion valvecoil.Check No. 01Check the outdoor heatexchanger thermistor.Check No. 17Check the installationcondition.Be sure to turn off the power switch before connecting or disconnectingconnectors, or parts may be damaged.