7.3.9 8-** Communication and OptionsPar. No. # Parameter description Default value 4-set-up Change duringoperationConver-sion indexType8-0* General Settings8-01 Control Site null All set-ups TRUE - Uint88-02 Control Source null All set-ups TRUE - Uint88-03 Control Timeout Time SR 1 set-up TRUE -1 Uint328-04 Control Timeout Function [0] Off 1 set-up TRUE - Uint88-05 End-of-Timeout Function [1] Resume set-up 1 set-up TRUE - Uint88-06 Reset Control Timeout [0] Do not reset All set-ups TRUE - Uint88-07 Diagnosis Trigger [0] Disable 2 set-ups TRUE - Uint88-1* Control Settings8-10 Control Profile [0] FC profile All set-ups FALSE - Uint88-13 Configurable Status Word STW [1] Profile Default All set-ups TRUE - Uint88-3* FC Port Settings8-30 Protocol null 1 set-up TRUE - Uint88-31 Address SR 1 set-up TRUE 0 Uint88-32 Baud Rate null 1 set-up TRUE - Uint88-33 Parity / Stop Bits null 1 set-up TRUE - Uint88-34 Estimated cycle time 0 ms 2 set-ups TRUE -3 Uint328-35 Minimum Response Delay SR 1 set-up TRUE -3 Uint168-36 Maximum Response Delay SR 1 set-up TRUE -3 Uint168-37 Maximum Inter-Char Delay SR 1 set-up TRUE -5 Uint168-4* FC MC protocol set8-40 Telegram Selection [1] Standard telegram 1 2 set-ups TRUE - Uint88-42 PCD write configuration SR All set-ups TRUE - Uint168-43 PCD read configuration SR All set-ups TRUE - Uint168-5* Digital/Bus8-50 Coasting Select [3] Logic OR All set-ups TRUE - Uint88-52 DC Brake Select [3] Logic OR All set-ups TRUE - Uint88-53 Start Select [3] Logic OR All set-ups TRUE - Uint88-54 Reversing Select null All set-ups TRUE - Uint88-55 Set-up Select [3] Logic OR All set-ups TRUE - Uint88-56 Preset Reference Select [3] Logic OR All set-ups TRUE - Uint88-7* BACnet8-70 BACnet Device Instance 1 N/A 1 set-up TRUE 0 Uint328-72 MS/TP Max Masters 127 N/A 1 set-up TRUE 0 Uint88-73 MS/TP Max Info Frames 1 N/A 1 set-up TRUE 0 Uint168-74 "I-Am" Service [0] Send at power-up 1 set-up TRUE - Uint88-75 Initialisation Password SR 1 set-up TRUE 0 VisStr[20]8-8* FC Port Diagnostics8-80 Bus Message Count 0 N/A All set-ups TRUE 0 Uint328-81 Bus Error Count 0 N/A All set-ups TRUE 0 Uint328-82 Slave Messages Rcvd 0 N/A All set-ups TRUE 0 Uint328-83 Slave Error Count 0 N/A All set-ups TRUE 0 Uint328-84 Slave Messages Sent 0 N/A All set-ups TRUE 0 Uint328-85 Slave Timeout Errors 0 N/A All set-ups TRUE 0 Uint328-89 Diagnostics Count 0 N/A 1 set-up TRUE 0 Int328-9* Bus Jog / Feedback8-90 Bus Jog 1 Speed 100 RPM All set-ups TRUE 67 Uint168-91 Bus Jog 2 Speed 200 RPM All set-ups TRUE 67 Uint168-94 Bus Feedback 1 0 N/A 1 set-up TRUE 0 N28-95 Bus Feedback 2 0 N/A 1 set-up TRUE 0 N28-96 Bus Feedback 3 0 N/A 1 set-up TRUE 0 N2How to Programme the Frequ... VLT® HVAC Drive Operating Instructions104 MG.11.AD.02 - VLT® is a registered Danfoss trademark77