5 Commissioning and ApplicationExamples5.1 Commissioning5.1.1 Quick Menu ModeParameter DataThe graphical display (GLCP) provides access to all parameterslisted under the Quick Menus. The numeric display (NLCP) onlyprovides access to the Quick Setup parameters. To set parame-ters using the [Quick Menu] button - enter or change parame-ter data or settings in accordance with the followingprocedure:1. Press Quick Menu button2. Use the [▲] and [▼] buttons to find the parameteryou want to change3. Press [OK]4. Use [▲] and [▼] buttons to select the correct parame-ter setting5. Press [OK]6. To move to a different digit within a parametersetting, use the [◀] and [▶] buttons7. Highlighted area indicates digit selected for change8. Press [Cancel] button to disregard change, or press[OK] to accept change and enter the new settingExample of changing parameter dataAssume parameter 22-60 is set to [Off]. However, you want tomonitor the fan-belt condition - non- broken or broken -according to the following procedure:1. Press Quick Menu key2. Choose Function Setups with the [▼] button3. Press [OK]4. Choose Application Settings with the [▼] button5. Press [OK]6. Press [OK] again for Fan Functions7. Choose Broken Belt Function by pressing [OK]8. With [▼] button, choose [2] TripThe frequency converter will now trip if a broken fan-belt isdetected.Select [My Personal Menu] to display personal parameters:For example, an AHU or pump OEM may have pre-program-med personal parameters to be in My Personal Menu duringfactory commissioning to make on-site commissioning/finetuning simpler. These parameters are selected in par. 0-25 MyPersonal Menu. Up to 20 different parameters can be program-med in this menu.Select [Changes Made] to get information about:• The last 10 changes. Use the up/down navigationkeys to scroll between the last 10 changed parame-ters.• The changes made since default setting.Select [Loggings]:to get information about the display line read-outs. Theinformation is shown as graphs.Only display parameters selected in par. 0-20 Display Line 1.1Small and par. 0-24 Display Line 3 Large can be viewed. It ispossible to store up to 120 samples in the memory for laterreference.Quick SetupEfficient Parameter Set-up for VLT HVAC Drive Applications:The parameters can easily be set up for the vast majority ofthe VLT HVAC Drive applications only by using the [QuickSetup] option.After pressing [Quick Menu], the different choices in the QuickMenu are listed. See also illustration 6.1 below and tables Q3-1to Q3-4 in the followingFunction Setups section.Example of using the Quick Setup option:Assume you want to set the Ramp Down Time to 100 seconds:1. Select [Quick Setup]. The first par. 0-01 Language inQuick Setup appears2. Press [▼] repeatedly until par. 3-42 Ramp 1 RampDown Time appears with the default setting of 20seconds3. Press [OK]4. Use the [◀] button to highlight the 3rd digit beforethe comma5. Change '0' to '1' by using the [▲] button6. Use the [▶] button to highlight the digit '2'7. Change '2' to '0' with the [▼] button8. Press [OK]The new ramp-down time is now set to 100 seconds.It is recommended to do the set-up in the order listed.Commissioning and Applicati... VLT® HVAC Drive Operating InstructionsMG.11.AD.02 - VLT® is a registered Danfoss trademark 475 5