7 Application Examples7.1 IntroductionThe examples in this section are intended as a quickreference for common applications.• Parameter settings are the regional default valuesunless otherwise indicated (selected in0-03 Regional Settings).• Parameters associated with the terminals andtheir settings are shown next to the drawings.• Where switch settings for analog terminals A53 orA54 are required, these are also shown.7.2 Application ExamplesCAUTIONThermistors must use reinforced or double insulation tomeet PELV insulation requirements.ParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOM12131819202729323337505354554239130BB929.10Function Setting1-29 AutomaticMotorAdaptation(AMA)[1] EnablecompleteAMA5-12 Terminal 27Digital Input[2]* Coastinverse*=Default ValueNotes/comments: Parametergroup 1–2* Motor Data must beset according to motorTable 7.1 AMA with T27 ConnectedParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOM12131819202729323337505354554239130BB930.10Function Setting1-29 AutomaticMotorAdaptation(AMA)[1] EnablecompleteAMA5-12 Terminal 27Digital Input[0] Nooperation*=Default ValueNotes/comments: Parametergroup 1–2* Motor Data must beset according to motorTable 7.2 AMA without T27 ConnectedParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOM12131819202729323337505354554239A53U - I-10 - +10V+-130BB926.10Function Setting6-10 Terminal 53Low Voltage0.07 V*6-11 Terminal 53High Voltage10 V*6-14 Terminal 53Low Ref./Feedb.Value0 RPM6-15 Terminal 53High Ref./Feedb.Value1,500 RPM*=Default ValueNotes/comments:Table 7.3 Analog Speed Reference (Voltage)Application Examples Operating InstructionsMG16D302 Danfoss A/S © Rev. 06/2014 All rights reserved. 537 7