Digital outputProgrammable digital/pulse outputs 2Terminal number 27, 29 1)Voltage level at digital/frequency output 0-24 VMax. output current (sink or source) 40 mAMax. load at frequency output 1 kΩMax. capacitive load at frequency output 10 nFMinimum output frequency at frequency output 0 HzMaximum output frequency at frequency output 32 kHzAccuracy of frequency output Max. error: 0.1% of full scaleResolution of frequency outputs 12 bit1) Terminal 27 and 29 can also be programmed as input.The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.Control card, 24 V DC outputTerminal number 12, 13Max. load 200 mAThe 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digitalinputs and outputs.Relay outputsProgrammable relay outputs 2Relay 01 Terminal number 1-3 (break), 1-2 (make)Max. terminal load (AC-1)1) on 1-2 (NO) (Resistive load)2),3) 400 V AC, 2 AMax. terminal load (AC-15)1) on 1-2 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 AMax. terminal load (DC-1)1) on 1-2 (NO) (Resistive load) 80 V DC, 2 AMax. terminal load (DC-13)1) on 1-2 (NO) (Inductive load) 24 V DC, 0.1 AMax. terminal load (AC-1)1) on 1-3 (NC) (Resistive load) 240 V AC, 2 AMax. terminal load (AC-15)1) on 1-3 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 AMax. terminal load (DC-1)1) on 1-3 (NC) (Resistive load) 50 V DC, 2 AMax. terminal load (DC-13)1) on 1-3 (NC) (Inductive load) 24 V DC, 0.1 AMin. terminal load on 1-3 (NC), 1-2 (NO) 24 V DC 10 mA, 24V AC 2 mAEnvironment according to EN 60664-1 overvoltage category III/pollution degree 2Relay 02 Terminal number 4-6 (break), 4-5 (make)Max. terminal load (AC-1)1) on 4-5 (NO) (Resistive load)2)3) 400 V AC, 2 AMax. terminal load (AC-15)1) on 4-5 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 AMax. terminal load (DC-1)1) on 4-5 (NO) (Resistive load) 80 V DC, 2 AMax. terminal load (DC-13)1) on 4-5 (NO) (Inductive load) 24 V DC, 0.1 AMax. terminal load (AC-1)1) on 4-6 (NC) (Resistive load) 240 V AC, 2 AMax. terminal load (AC-15)1) on 4-6 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 AMax. terminal load (DC-1)1) on 4-6 (NC) (Resistive load) 50 V DC, 2 AMax. terminal load (DC-13)1) on 4-6 (NC) (Inductive load) 24 V DC, 0.1 AMin. terminal load on 4-6 (NC), 4-5 (NO) 24 V DC 10 mA, 24V AC 2 mAEnvironment according to EN 60664-1 overvoltage category III/pollution degree 21) IEC 60947 t 4 and 5The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).2) Overvoltage Category II3) UL applications 300 V AC 2 AControl card, 10 V DC outputTerminal number 50Output voltage 10.5 V ±0.5 VMax. load 25 mAThe 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.Specifications Operating InstructionsMG16D302 Danfoss A/S © Rev. 06/2014 All rights reserved. 8111 11