8vacon • 52 APPENDIX 2 - CONTROL AND STATUS WORDLocal contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/8.2 Status Word DescriptionsThe Status word is composed of 32 bits. FBFixedStatusWord consist of the first 16 bits. FBGen-eralStatusWord consist of the remaining 16 bits. While the functionality of FBFixedStatusWord isfixed in the VACON® standard applications, the functionality of FBGeneralStatusWord is totallyapplication specific and can vary even in the VACON® standard applications.The meanings of FBFixedStatusWord bits are described below. Unused bits have to be set to zero..Table 51. FBFixedStatusWord bitsBit Function DescriptionB0 Ready 0 Drive is not ready.1 Drive is ready to run.B1 Run 0 Motor is not running.1 Motor is running.B2 Direction 0 Motor is running clockwise.1 Motor is running counterclockwise.B3 Fault 0 No fault active.1 Drive has an active fault.B4 Alarm 0 No alarm active.1 Drive has active alarm.B5 At reference 0 Motor is not running at reference speed.1 Motor is running at reference speed.B6 Zero speed 0 Motor is not at zero speed.1 Motor is running at zero speed.B7 Flux ready 0 Motor is not magnetized.1 Motor is magnetized.B8-B12 Reserved