Pump A pump is to run at six different speeds, determined byshifting between the preset references.Switch no.:1 3 40 0 0 Preset reference 10 0 1 Preset reference 20 1 0 Preset reference 30 1 1 Preset reference 41 0 0 Preset reference 51 0 1 Preset reference 6When switch 1 is active, a setup change to setup 2 ismade.Start/stop by means of switch 21. Choice of Setup, lsb2. Start/stop3. Preset reference, lsb4. Preset reference, msbThe following must be programmed in order shown:Function: Parameter: Setting: Data value:Active Setup 004 Multi-Setup [5]Digital input, term. 16 300 Choice of Setup, lsb [10]Digital input, term. 32 306 Preset reference, lsb [6]Digital input, term. 33 307 Preset reference, msb [6]Setup copying 006 Copy to Setup 2 from # [2]Edit Setup 005 Setup 1 [1]Maximum reference 205 60Preset reference 1 215 10%Preset reference 2 216 20%Preset reference 3 217 30%Preset reference 4 218 40%Edit Setup 005 Setup 2 [2]Maximum reference 205 60Preset reference 5 215 70%Preset reference 6 216 100%All other settings are based on factory settings. However, motor data (nameplate data) must always be entered in parameters 102-106.VLT ® 5000 Design GuideMG.52.B2.02 - VLT ® is a registered Danfoss trademark 101Connection example