Electrical dataBookstyle and Compact, Mains supply 3 x 200 - 240 VAccording to international requirements VLT type 5001 5002 5003 5004 5005 5006Output current IVLT,N [A] 3.7 5.4 7.8 10.6 12.5 15.2I VLT, MAX (60 s) [A] 5.9 8.6 12.5 17 20 24.3Output (240 V) SVLT,N [kVA] 1.5 2.2 3.2 4.4 5.2 6.3Typical shaft output P VLT,N [kW] 0.75 1.1 1.5 2.2 3.0 3.7Typical shaft output P VLT,N [HP] 1 1.5 2 3 4 5Max. cable cross-section to motor,brake and loadsharing [mm 2 ]/[AWG]2 ) 4/10 4/10 4/10 4/10 4/10 4/10Rated input current (200 V)IL,N [A] 3.4 4.8 7.1 9.5 11.5 14.5Max. cablecross-section power [mm 2 ]/[AWG] 2 ) 4/10 4/10 4/10 4/10 4/10 4/10Max. pre-fuses [-]/UL1) [A] 16/10 16/10 16/15 25/20 25/25 35/30Efficiency 3) 0.95 0.95 0.95 0.95 0.95 0.95Weight IP 20 EB Bookstyle [kg] 7 7 7 9 9 9.5Weight IP 20 EB Compact [kg] 8 8 8 10 10 10Weight IP 54 Compact [kg] 11.5 11.5 11.5 13.5 13.5 13.5Power loss atmax. load. [W] 58 76 95 126 172 194Enclosure IP 20/IP54IP 20/IP54IP 20/IP54IP 20/IP54IP 20/IP54IP 20/IP541. For type of fuse see section Fuses.2. American Wire Gauge.3. Measured using 30 m screened motor cables at rated load and rated frequency.VLT ® 5000 Design GuideMG.52.B2.02 - VLT ® is a registered Danfoss trademark 37Technical data