VLT ® 8000 AQUAProgramming■ Warning words 1+2 and Alarm wordWarning word, extended status word and alarm wordare shown in Hex format on the display. If thereis more than one warning or alarm, a sum of thetotal warnings or alarms will be shown.The descriptions relating to the extended status wordcan be seen from in Status word as per FC protocol,and with respect to warning word, extended statusword and alarm word, the descriptions can also beread out via the serial bus in parameter 531 Warningword, 532 Extended status word and 529 Alarm word.Hex code Extended status word00000001 Overvoltage control active00000002 Start delay00000004 Sleep boost active00000008 Sleep mode active00000010 Automatic motor adaptationcompleted00000020 Automatic motor adaptationrunning00000040 Reversing and start00000080 Ramp operation00000100 Reversing00000200 Speed = reference00000400 Running00000800 Local ref. = 1,Remote controlled ref. = 000001000 OFF mode = 100002000 Auto mode = 0, Hand mode = 100004000 Start blocked00008000 Start blocked signal missing00010000 Freeze output00020000 Freeze output blocked00040000 Jogging00080000 Jog blocked00100000 Stand by00200000 Stop00400000 DC stop00800000 Drive ready01000000 Relay 123 active02000000 Drive ready04000000 Control ready08000000 Start prevented10000000 Profibus OFF3 active20000000 Profibus OFF2 active40000000 Profibus OFF1 active80000000 ReservedHex code Warning word 200000010 Dry runHex code Warning word00000001 Reference high00000002 Fault in EEprom on control card00000004 Fault in EEprom on power card00000008 HPFB bus timeout00000010 Serial communication timeout00000020 Overcurrent00000040 Current limit00000080 Motor thermistor00000100 Motor overtemperature00000200 Inverter overtemperature00000400 Undervoltage00000800 Overvoltage00001000 Voltage warning low00002000 Voltage warning high00004000 Mains failure00008000 Live zero fault00010000 Under 10 Volt (terminal 50)00020000 Reference low00040000 Feedback high00080000 Feedback low00100000 Output current high00200000 Out of frequency range00400000 Profibus communication fault00800000 Output current low01000000 Output frequency high02000000 Output frequency low04000000 AMA - motor too small08000000 AMA - motor too big10000000 AMA - check par. 102, 103, 10520000000 AMA - check par. 102, 104, 10640000000 Reserved80000000 ReservedBit (Hex) Alarm word0000 0001 Unknown alarm0000 0002 Trip locked0000 0004 Automatic motor adaption fault0000 0008 HPFB seriel communicationtimeout0000 0010 Basic serial communicationtimeout0000 0020 Short circuit0000 0040 Switch mode fault0000 0080 Earth fault0000 0100 Over current0000 0200 Current limit0000 0400 Motor thermistor0000 0800 Motor overload0000 1000 Inverter overload0000 2000 Under voltage0000 4000 Over voltage0000 8000 Mains imbalance0001 0000 Live zero fault0002 0000 Heat sink temperature too high0004 0000 Motor phase W missing0008 0000 Motor phase V missing0010 0000 Motor phase U missing0020 0000 HPFB seriel communication fault0040 0000 Gate drive fault0080 0000 Output current low0100 0000 Safety interlock0200 0000 Reserved0400 0000 Dry run(Remaining bits reserved for future use)MG.83.A2.02 - VLT is a registered Danfoss trademark 167