6.3 Description of Parameters6.3.1 Main MenuThe main menu includes all available parameters in theVLT® Active Filter. All parameters are grouped by nameindicating the function of the parameter group. Allparameters are listed by name and number in this manual.6.4 0-** Operation/DisplayParameters in this group are related to the fundamentalfunctions of the active filter, function of the LCP keys, andconfiguration of the LCP display.6.4.1 0-0* Basic Settings0-01 LanguageOption: Function:Defines the language to be used in thedisplay. The filter can be delivered with 4different language packages. English andGerman are included in all packages.English cannot be erased or manipulated.[0] * English Part of Language packages 1 - 4[1] Deutsch Part of Language packages 1 - 4[2] Francais Part of Language package 1[3] Dansk Part of Language package 1[4] Spanish Part of Language package 1[5] Italiano Part of Language package 1[6] Svenska Part of Language package 1[7] Nederlands Part of Language package 1[10] Chinese Part of Language package 2[20] Suomi Part of Language package 1[22] English US Part of Language package 4[27] Greek Part of Language package 4[28] Bras.port Part of Language package 4[36] Slovenian Part of Language package 3[39] Korean Part of Language package 2[40] Japanese Part of Language package 2[41] Turkish Part of Language package 4[42] Trad.Chinese Part of Language package 2[43] Bulgarian Part of Language package 3[44] Srpski Part of Language package 3[45] Romanian Part of Language package 30-01 LanguageOption: Function:[46] Magyar Part of Language package 3[47] Czech Part of Language package 3[48] Polski Part of Language package 4[49] Russian Part of Language package 3[50] Thai Part of Language package 2[51] BahasaIndonesiaPart of Language package 2[52] Hrvatski0-04 Operating State at Power-up (Hand)Option: Function:Selects the operating mode uponreconnection of the filter to mains voltageafter power down in Hand (local) operationmode.[0] Resume Restarts the filter maintaining the same start/stop settings (applied by [HAND ON/OFF]) asbefore the filter was powered down.[1] * Forced stop Restarts the filter with a saved local reference,after mains voltage reappears and afterpressing [HAND ON].6.4.2 0-1* Set-up OperationsDefine and control the individual parameter set-ups.The active filter has 4 parameter set-ups that can beprogrammed independently of one another, making itflexible.The active set-up (the set-up in which the active filter iscurrently operating) can be selected inparameter 0-10 Active Set-up and is displayed on the LCP.Using multi set-up, it is possible to switch between set-upswith the active filter running or stopped, via digital inputor serial communication commands. If it is necessary tochange set-ups while running, ensure thatparameter 0-12 This Set-up Linked to is programmed asrequired. Using parameter 0-11 Edit Set-up, it is possible toedit parameters within any of the set-ups while continuingthe active filter operation in its active set-up, which can bea different set-up than the one being edited.Use parameter 0-51 Set-up Copy to copy parameter settingsbetween the set-ups enabling faster commissioning ifsimilar parameter settings are required in different set-ups.Applications and Basic Prog... Operating InstructionsMG90V302 Danfoss A/S © 09/2014 All rights reserved. 416 6