6.12.3 5-** Digital In/OutPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType5-0* Digital I/O mode5-00 Digital I/O mode [0] PNP All set-ups FALSE - Uint85-01 Terminal 27 mode [0] Input All set-ups TRUE - Uint85-02 Terminal 29 mode [0] Input All set-ups TRUE - Uint85-1* Digital Inputs5-10 Terminal 18 digital input [8] Start All set-ups TRUE - Uint85-11 Terminal 19 digital input [0] No operation All set-ups TRUE - Uint85-12 Terminal 27 digital input [0] No operation All set-ups TRUE - Uint85-13 Terminal 29 digital input [0] No operation All set-ups TRUE - Uint85-16 Terminal X30/2 digital input [0] No operation All set-ups TRUE - Uint85-17 Terminal X30/3 digital input [0] No operation All set-ups TRUE - Uint85-18 Terminal X30/4 digital input [0] No operation All set-ups TRUE - Uint85-19 Terminal 37 Safe stop [1] Safe Stop Alarm 1 set-up TRUE - Uint85-3* Digital Outputs5-30 Terminal 27 Digital output [0] No operation All set-ups TRUE - Uint85-31 Terminal 29 Digital output [0] No operation All set-ups TRUE - Uint85-4* Relays5-40 Function relay [0] No operation All set-ups TRUE - Uint85-41 On delay, relay 0.30 s All set-ups TRUE -2 Uint165-42 Off delay, relay 0.30 s All set-ups TRUE -2 Uint166.12.4 8-** Comm. and OptionsPar.No. #Parameter description Default value 4-set-up ChangeduringoperationConver-sion indexType8-0* General Settings8-01 Control site [0] Digital and ctrl.word All set-ups TRUE - Uint88-02 Control word source null All set-ups TRUE - Uint88-03 Control word timeout time 1.0 s 1 set-up TRUE -1 Uint328-04 Control word timeout function [0] Off 1 set-up TRUE - Uint88-05 End-of-timeout Function [1] Resume set-up 1 set-up TRUE - Uint88-06 Reset control word timeout [0] Do not reset All set-ups TRUE - Uint88-3* FC Port Settings8-30 Protocol [1] FC MC 1 set-up TRUE - Uint88-31 Address 2 N/A 1 set-up TRUE 0 Uint88-32 FC port baud rate [2] 9600 Baud 1 set-up TRUE - Uint88-35 Minimum response delay 10 ms All set-ups TRUE -3 Uint168-36 Max response delay 5000 ms 1 set-up TRUE -3 Uint168-37 Max Iiter-char delay 25 ms 1 set-up TRUE -3 Uint168-5* Digital/Bus8-53 Start select [3] Logic OR All set-ups TRUE - Uint88-55 Set-up select [3] Logic OR All set-ups TRUE - Uint8Applications and Basic Prog... Operating Instructions64 Danfoss A/S © 09/2014 All rights reserved. MG90V30266