Recommended max. fusePower [kW] BussmannType RK1BussmannType JBussmannType TBussmannType CCBussmannType CCBussmannType CC0.75-1.1 KTS-R-5 JKS-5 JJS-6 FNQ-R-5 KTK-R-5 LP-CC-51.5-2.2 KTS-R-10 JKS-10 JJS-10 FNQ-R-10 KTK-R-10 LP-CC-103 KTS-R15 JKS-15 JJS-15 FNQ-R-15 KTK-R-15 LP-CC-154 KTS-R20 JKS-20 JJS-20 FNQ-R-20 KTK-R-20 LP-CC-205.5 KTS-R-25 JKS-25 JJS-25 FNQ-R-25 KTK-R-25 LP-CC-257.5 KTS-R-30 JKS-30 JJS-30 FNQ-R-30 KTK-R-30 LP-CC-3011-15 KTS-R-35 JKS-35 JJS-35 - - -18 KTS-R-45 JKS-45 JJS-45 - - -22 KTS-R-50 JKS-50 JJS-50 - - -30 KTS-R-60 JKS-60 JJS-60 - - -37 KTS-R-80 JKS-80 JJS-80 - - -45 KTS-R-100 JKS-100 JJS-100 - - -55 KTS-R-125 JKS-125 JJS-125 - - -75 KTS-R-150 JKS-150 JJS-150 - - -90 KTS-R-175 JKS-175 JJS-175 - - -Table 10.24 3 x 525-600 V, Frame Sizes A, B and CRecommended max. fusePower [kW] SIBAType RK1Littel fuseType RK1Ferraz-ShawmutType RK1Ferraz-ShawmutJ0.75-1.1 5017906-005 KLS-R-005 A6K-5-R HSJ-61.5-2.2 5017906-010 KLS-R-010 A6K-10-R HSJ-103 5017906-016 KLS-R-015 A6K-15-R HSJ-154 5017906-020 KLS-R-020 A6K-20-R HSJ-205.5 5017906-025 KLS-R-025 A6K-25-R HSJ-257.5 5017906-030 KLS-R-030 A6K-30-R HSJ-3011-15 5014006-040 KLS-R-035 A6K-35-R HSJ-3518 5014006-050 KLS-R-045 A6K-45-R HSJ-4522 5014006-050 KLS-R-050 A6K-50-R HSJ-5030 5014006-063 KLS-R-060 A6K-60-R HSJ-6037 5014006-080 KLS-R-075 A6K-80-R HSJ-8045 5014006-100 KLS-R-100 A6K-100-R HSJ-10055 2028220-125 KLS-R-125 A6K-125-R HSJ-12575 2028220-150 KLS-R-150 A6K-150-R HSJ-15090 2028220-200 KLS-R-175 A6K-175-R HSJ-175Table 10.25 3 x 525-600 V, Frame Sizes A, B and C1) 170M fuses shown from Bussmann use the -/80 visual indicator. –TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size andamperage may be substituted.Specifications VLT® AQUA DriveOperating Instructions80 MG20M902 - VLT® is a registered Danfoss trademark1010Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net