3.15 Parameters: 15-** Drive Information3.15.1 15-0* Operating Data15-00 Operating hoursRange: Function:0 h* [0 - 2147483647 h] View how many hours the frequencyconverter has run. The value is savedwhen the frequency converter isturned off.15-01 Running HoursRange: Function:0 h* [0 -2147483647 h]View how many hours the motor has run.Reset the counter inparameter 15-07 Reset Running HoursCounter. The value is saved when thefrequency converter is turned off.15-02 kWh CounterRange: Function:0 kWh* [0 -2147483647kWh]Register the power consumption ofthe motor as an average value over 1hour. Reset the counter inparameter 15-06 Reset kWh Counter.15-03 Power Up'sRange: Function:0* [0 - 2147483647 ] View the number of times the frequencyconverter has been powered up.15-04 Over Temp'sRange: Function:0* [0 - 65535 ] View the number of frequency convertertemperature faults.15-05 Over Volt'sRange: Function:0* [0 - 65535 ] View the number of frequency converterovervoltages.15-06 Reset kWh CounterOption: Function:[0] * Do not reset No reset of the kWh counter is required.[1] Reset counter Press [OK] to reset the kWh counter to 0(see parameter 15-02 kWh Counter).15-07 Reset Running Hours CounterOption: Function:[0] * Do notreset[1] ResetcounterTo reset the running hours counter to 0, select[1] Reset and press [OK] (seeparameter 15-01 Running Hours). This15-07 Reset Running Hours CounterOption: Function:parameter cannot be selected via the serialport, RS485.Select [0] Do not reset if no reset of therunning-hours counter is required.3.15.2 15-1* Data Log SettingsThe data log enables continuous logging of up to 4 datasources (parameter 15-10 Logging Source) at individual rates(parameter 15-11 Logging Interval). A trigger event(parameter 15-12 Trigger Event) and window(parameter 15-14 Samples Before Trigger) are used to startand stop the logging conditionally.15-10 Logging SourceOption: Function:Select which variablesare to be logged.[0] * None[15] Readout: actual setup[1397] Alert Alarm Word[1398] Alert Warning Word[1399] Alert Status Word[1472] Legacy Alarm Word[1473] Legacy Warning Word[1474] Leg. Ext. Status Word[1600] Control Word[1601] Reference [Unit][1602] Reference %[1603] Status Word[1606] Actual Position[1607] Target Position This option is onlyavailable for softwareversion 48.XX[1608] Position Error This option is onlyavailable for softwareversion 48.XX[1610] Power [kW][1611] Power [hp][1612] Motor Voltage[1613] Frequency[1614] Motor current[1616] Torque [Nm][1617] Speed [RPM][1618] Motor Thermal[1620] Motor Angle[1621] Torque [%] High Res.[1622] Torque [%][1624] Calibrated Stator Resistance[1625] Torque [Nm] HighParameter Descriptions VLT® AutomationDrive FC 301/302202 Danfoss A/S © 10/2018 All rights reserved. MG33MP0233