3.8 Parameters: 6-** Analog In/Out3.8.1 6-0* Analog I/O ModeThe analog inputs can freely be allocated to be eithervoltage (FC 301: 0..10 V, FC 302: 0..± 10 V) or current (FC301/FC 302: 0/4..20 mA) input.NOTICEThermistors may be connected to either an analog or adigital input.6-00 Live Zero Timeout TimeRange: Function:10 s* [1 -99 s]Enter the live zero timeout time period. Live zerotimeout time is active for analog inputs, that is,terminal 53 or terminal 54, used as reference orfeedback sources. If the reference signal valueassociated with the selected current input dropsbelow 50% of the value set in 6-10 Terminal 53Low Voltage, 6-12 Terminal 53 Low Current,6-20 Terminal 54 Low Voltage or 6-22 Terminal 54Low Current for a time period longer than thetime set in parameter 6-00 Live Zero Timeout Time,the function selected in 6-01 Live Zero TimeoutFunction is activated.6-01 Live Zero Timeout FunctionOption: Function:Select the timeout function. The function setin parameter 6-01 Live Zero Timeout Function isactivated, if the input signal on terminal 53 or54 is below 50% of the value inparameter 6-10 Terminal 53 Low Voltage,parameter 6-12 Terminal 53 Low Current,parameter 6-20 Terminal 54 Low Voltage orparameter 6-22 Terminal 54 Low Current for atime period defined in parameter 6-00 Live ZeroTimeout Time. If several timeouts occursimultaneously, the frequency converterprioritises the timeout functions as follows:1. Parameter 6-01 Live Zero TimeoutFunction.2. Parameter 8-04 Control Word TimeoutFunction.[0] * Off[1] FreezeoutputFrozen at the present value.[2] Stop Overruled to stop.[3] Jogging Overruled to jog speed.[4] Max. speed Overruled to max. speed.[5] Stop andtripOverruled to stop with subsequent trip.[20] Coast6-01 Live Zero Timeout FunctionOption: Function:[21] Coast andtrip3.8.2 6-1* Analog Input 1Parameters for configuring the scaling and limits foranalog input 1 (terminal 53).Ex. 5 V 10 V30060090012001500150130BT103.101 VPar 6-xx'Low Voltage'or'Low Current'Par 6-xx'High Voltage'or'High Current'Analog inputRef./Feedback[RPM]Par 6-xx'High Ref./Feedb. Value'Par 6-xx'Low Ref./Feedb. Value'Illustration 3.41 Analog Input 16-10 Terminal 53 Low VoltageRange: Function:0.07 V* [ -10.00 -par. 6-11 V]Enter the low voltage value. This analoginput scaling value should correspond tothe minimum reference value, set inparameter 6-14 Terminal 53 Low Ref./Feedb.Value. See also the section ReferenceHandling.6-11 Terminal 53 High VoltageRange: Function:10 V* [ par. 6-10 -10 V]Enter the high-voltage value. This analoginput scaling value should correspond tothe high reference/feedback value set in6-15 Terminal 53 High Ref./Feedb. Value.6-12 Terminal 53 Low CurrentRange: Function:0.14mA*[ 0 -par. 6-13mA]Enter the low current value. This referencesignal should correspond to the minimumreference value, set inparameter 3-02 Minimum Reference. The valuemust be set at >2 mA in order to activate theLive Zero Timeout Function inparameter 6-01 Live Zero Timeout Function.Parameter Descriptions VLT® AutomationDrive FC 301/302102 Danfoss A/S © Rev. 10/2014 All rights reserved. MG33MJ0233