4 Parameter Descriptions4.1 Parameters: 0-** Operation and DisplayParameters related to the fundamental functions of thefrequency converter, function of the LCP keys, and configu-ration of the LCP display.4.1.1 0-0* Basic Settings0-01 LanguageOption: Function:[0] * English[10] Chinese[28] Portuguese0-03 Regional SettingsOption: Function:NOTICEThis parameter cannot be adjusted whilethe motor is running.[0] * Interna-tionalActivate parameter 1-20 Motor Power [kW] forsetting the motor power in kW and set thedefault value of parameter 1-23 Motor Frequencyto 50 Hz.[1] US Activate parameter 1-20 Motor Power [kW] forsetting the motor power in hp and set thedefault value of parameter 1-23 Motor Frequencyto 60 Hz.0-04 Operating State at Power-up (Hand)Option: Function:Select the operating mode uponreconnection of the frequency converter tomains voltage after power down in hand-onmode.[0] Resume Restart the frequency converter, maintainingthe start/stop settings (applied by [Hand On/Off]) selected before the power-down of thefrequency converter.[1] * Forced stop,ref=oldRestart the frequency converter with a savedlocal reference after mains voltage reappearsand after pressing [Hand On].[2] Forced stop,ref=0Reset the local reference to 0 upon restartingthe frequency converter.0-06 GridTypeOption: Function:Select the grid type of the supplyvoltage/frequency.NOTICENot all options are supported inall power sizes.IT grid is a supply mains, where theneutral point of secondary side of thetransformer is not connected toground.Delta is a supply mains where thesecondary part of the transformer isdelta-connected and 1 phase isconnected to ground.[10] 380-440V/50Hz/IT-grid[11] 380-440V/50Hz/Delta[12] 380-440V/50Hz[20] 440-480V/50Hz/IT-grid[21] 440-480V/50Hz/Delta[22] 440-480V/50Hz[110] 380-440V/60Hz/IT-grid[111] 380-440V/60Hz/Delta[112] 380-440V/60Hz[120] 440-480V/60Hz/IT-grid[121] 440-480V/60Hz/Delta[122] 440-480V/60Hz0-07 Auto DC BrakingOption: Function:Protective function against overvoltage at coast in ITgrid environment. This parameter is active only when[1] On is selected in this parameter.[0] Off This function is not active.[1] * On This function is active.Parameter Descriptions VLT® AutomationDrive FC 36024 Danfoss A/S © 06/2017 All rights reserved. MG06C70244