PTC / Thermistor ROFFON<800 Ω+10 V130BF694.10>2.9 kΩ555042 53 54Illustration 4.6 PTC Thermistor Connection - Analog InputInputdigital/analogSupply voltage Thresholdcutout valuesDigital 10 V <800 Ω - 2.9 kΩAnalog 10 V <800 Ω - 2.9 kΩTable 4.3 Threshold Cutout ValuesNOTICECheck that the selected supply voltage follows thespecification of the used thermistor element.1-93 Thermistor SourceOption: Function:NOTICEThis parameter cannot be changedwhile the motor is running.NOTICEDigital input should be set to [0] PNP- Active at 24 V inparameter 5-00 Digital Input Mode.Select the input to which the thermistor(PTC sensor) should be connected. If ananalog input in this parameter is set as asource, it cannot be used for otherpurpose, for example, reference, feedback.[0] * None[1] Analog Input53[2] Analog Input54[3] Digital input18[4] Digital input19[5] Digital input32[6] Digital input331-93 Thermistor SourceOption: Function:[7] Digital input314.3 Parameters: 2-** Brakes4.3.1 2-0* DC BrakeUse this parameter group to configure DC brake and DChold functions.2-00 DC Hold/Motor Preheat CurrentRange: Function:50 %*[0 -160 %]Set the holding current as a percentage of therated motor current IM,N parameter 1-24 MotorCurrent. This parameter holds the motor function(holding torque) or pre-heats the motor. Thisparameter is active if [0] DC hold is selected inparameter 1-72 Start Function, or if [1] DC hold/pre-heat is selected in parameter 1-80 Function atStop.NOTICEThe maximum value depends on the ratedmotor current. Avoid 100% current for toolong. It may damage the motor.2-01 DC Brake CurrentRange: Function:50%*[0 -150 %]NOTICEMOTOR OVERHEATINGThe maximum value depends on the ratedmotor current.To avoid motor damage caused byoverheating, do not run at 100% for toolong.Set current as % of rated motor current,parameter 1-24 Motor Current. When speed isbelow the limit set in parameter 2-04 DC Brake CutIn Speed, or when the DC-brake inverse function isactive (in parameter group 5-1* Digital Inputs set to[5] DC-brake inverse; or via the serial port), a DC-brake current is applied on a stop command. Seeparameter 2-02 DC Braking Time for duration.2-02 DC Braking TimeRange: Function:10 s* [0 - 60 s] Set the duration of the DC-brake current set inparameter 2-01 DC Brake Current, onceactivated.Parameter Descriptions Programming GuideMG06C702 Danfoss A/S © 06/2017 All rights reserved. 454 4