6 Specifications6.1 Clearances, Dimensions, and Weights6.1.1 ClearancesTo ensure sufficient air flow for the frequency converter, observe the minimum clearances listed in Table 6.1.When air flow is obstructed close to the frequency converter, ensure adequate inlet of cool air and exhaust of hot air fromthe unit.Enclosure Power1)[kW (hp)]Clearance at ends[mm (in)]EnclosuresizeProtection rating 3x380–480 V Motor flange end Cooling fan endFCP 106 FCM 106MH1 IP66/Type 4X2) IP55/Type 12 0.55–1.5 (0.75–2.0) 30 (1.2) 100 (4.0)MH2 IP66/Type 4X2) IP55/Type 12 2.2–4.0 (3.0–5.0) 40 (1.6) 100 (4.0)MH3 IP66/Type 4X2) IP55/Type 12 5.5–7.5 (7.5–10) 50 (2.0) 100 (4.0)Table 6.1 Minimum Clearance for Cooling1) Power ratings relate to NO, see chapter 6.2 Electrical Data.2) The stated IP and Type rating only apply when the FCP 106 is mounted on a wall mount plate or a motor with the adapter plate. Ensure thatthe gasket between the adapter plate and the motor has a protection rating corresponding to the required rating for the combined motor andfrequency converter. As standalone frequency converter, the enclosure rating is IP00 and Open type.Enclosure size Maximum depth of hole into adapter plate (A) [mm(in)]Maximum height of screw above adapter plate (B)[mm (in)]MH1 3 (0.12) 0.5 (0.02)MH2 4 (0.16) 0.5 (0.02)MH3 3.5 (0.14) 0.5 (0.02)Table 6.2 Details for Motor Adapter Plate ScrewsAB1 2195NA494.101 Adapter plate2 ScrewA Maximum depth of hole into adapter plateB Maximum height of screw above adapter plateIllustration 6.1 Screws to Fasten Motor Adapter PlateSpecifications Design GuideMG03M202 Danfoss A/S © 06/2016 All rights reserved. 596 6